Page 927 - 2018_IRC
P. 927

APPENDIX P



                included, use manufacturers’ tables and velocity rec-  air-conditioning  cooling  towers.  Future  demands
                ommendations.                                      placed on the public main as a result of large growth or
                                                                   expansion should be considered. The available pressure
         Note: For all examples, the following metric conversions are
         applicable.                                               will decrease as additional loads are placed on the pub-
                                                                   lic system.
           1 cubic foot per minute = 0.4719 L/s.
                                                                 2. Demand  load.  Estimate  the  supply  demand  of  the
                                2
           1 square foot = 0.0929 m .                              building main and the principal branches and risers of
           1 degree = 0.0175 rad.                                  the system by totaling the corresponding demand from
                                                                   the applicable part of Table AP103.3(3). When estimat-
           1 pound per square inch = 6.895 kPa.                    ing  peak demand, sizing methods typically use water
           1 inch = 25.4 mm.                                       supply fixture units (w.s.f.u.) [see Table AP103.3(2)].
                                                                   This  numerical  factor  measures  the  load-producing
           1 foot = 304.8 mm.                                      effect of a single plumbing fixture of a given kind. The
           1 gallon per minute = 3.785 L/m.                        use  of  fixture  units  can  be  applied  to  a  single  basic
                                                                   probability curve (or table), found in the various sizing
         AP103.3 Segmented loss method. The size of water service
         mains,  branch  mains  and  risers  by  the  segmented  loss  methods [see Table AP103.3(3)]. The fixture units are
         method,  must  be  determined  by  knowing  the  water  supply  then converted into a gpm (L/m) flow rate for estimat-
         demand [gpm (L/m)], available water pressure [psi (kPa)] and  ing demand.
         friction loss caused by the water meter and developed length  2.1. Estimate continuous supply demand in gpm (L/m)
         of pipe [feet (m)], including the equivalent length of fittings.  such as for lawn sprinklers, air conditioners, etc.,
         This design procedure is based on the following parameters:     and add the sum to the total demand for fixtures.
                                                                         The result is the estimated supply demand for the
           1. The calculated friction loss through each length of pipe.
                                                                         building supply. Fixture units cannot be applied to
           2. A system of pressure losses, the sum of which must not     constant-use  fixtures,  such  as  hose  bibbs,  lawn
              exceed  the  minimum  pressure  available  at  the  street  sprinklers and air conditioners. These types of fix-
              main or other source of supply.                            tures must be assigned the gpm (L/m) value.
           3. Pipe sizing based on estimated peak demand, total pres-  3. Selection of pipe size. This water pipe sizing procedure
              sure  losses  caused  by  difference  in  elevation,  equip-  is  based  on  a  system  of  pressure  requirements  and
              ment,  developed length  and  pressure  required  at  the  losses, the sum of which must not exceed the minimum
              most remote fixture; loss through taps in water main;  pressure available at the supply source. These pressures
              losses  through  fittings,  filters,  backflow  prevention  are as follows:
              devices, valves and pipe friction.
                                                                     3.1. Pressure  required  at  the  fixture  to  produce
           Because of the variable conditions encountered in hydrau-     required flow. See Section P2903.1 of this code
         lic  design,  it  is  impractical  to  specify  definite  and  detailed  and Section 604.3 of the International Plumb-
         rules for the sizing of the water piping system. Current sizing  ing Code.
         methods do not address the differences in the probability of
         use  and  flow  characteristics  of  fixtures  between  types  of  3.2. Static pressure loss or gain (because of head) is
         occupancies.  Creating  an  exact  model  of  predicting  the   computed at 0.433 psi per foot (9.8 kPa/m) of
         demand for a building is impossible and final studies assess-   elevation change.
         ing the impact of water conservation on demand are not yet  3.3. Loss  through  a  water  meter.  The  friction  or
         complete.  The  following  steps  are  necessary  for  the  seg-  pressure loss can be obtained from the manufac-
         mented loss method.                                             turer.
           1. Preliminary. Obtain the necessary information regard-  3.4. Loss  through  taps  in  water  main  [see  Table
              ing  the  minimum  daily  static  service  pressure  in  the  AP103.3(4)].
              area where the building is to be located. If the building  3.5. Loss  through  special  devices,  such  as  filters,
              supply is to be metered, obtain information regarding      softeners,  backflow  prevention  devices  and
              friction loss relative to the rate of flow for meters in the  pressure  regulators.  These  values  must  be
              range  of  sizes  to  be  used.  Friction  loss  data  can  be  obtained from the manufacturers.
              obtained from manufacturers of water meters. Enough
              pressure  must  be  available  to  overcome  all  system  3.6. Loss  through  valves  and  fittings  [see  Tables
              losses caused by friction and elevation so that plumbing   AP103.3(5) and AP103.3(6)]. Losses for these
              fixtures operate properly. Section 604.6 of the Interna-   items are calculated by converting to the equiv-
              tional Plumbing Code requires that the water distribu-     alent length  of  piping  and  adding  to  the  total
              tion  system  be  designed  for  the  minimum  pressure    pipe length.
              available  taking  into  consideration  pressure  fluctua-  3.7. Loss caused by pipe friction can be calculated
              tions. The lowest pressure must be selected to guaran-     where  the  pipe  size,  pipe  length  and  flow
              tee a continuous, adequate supply of water. The lowest     through  the  pipe  are  known.  With  these  three
              pressure in the public main usually occurs in the sum-     items, the friction loss can be determined using
              mer because of lawn sprinkling and supplying water for     Figures AP103.3(2) through AP103.3(7). Where

         902                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   922   923   924   925   926   927   928   929   930   931   932