APPENDIX R



           Rain-exposed clay plasters shall be finished with a lime-
           based or silicate-mineral coating.
           AR103.5.3  Separation  of  wood  and  plaster.  Where
           wood framing occurs in light straw-clay walls, such wood
           surfaces  shall  be  separated  from  exterior  plaster  with
           No.15 asphalt felt, Grade D paper or other approved mate-
           rial except where the wood is preservative treated or natu-
           rally durable.
              Exception: Exterior clay plasters shall not be required
              to be separated from wood.
           AR103.5.4  Bridging  across  dissimilar  substrates.
           Bridging  shall  be  installed  across  dissimilar  substrates
           prior  to  the  application  of  plaster.  Acceptable  bridging
           materials include: expanded metal lath, woven wire mesh,
           welded wire mesh, fiberglass mesh, reed matting or bur-
           lap. Bridging shall extend not less than 4 inches (102 mm),
           on both sides of the juncture.
           AR103.5.5 Exterior cladding. Exterior cladding shall be
           spaced  not  less  than  /   inch  (19.1  mm)  from  the  light
                              1
                               2
           straw-clay such that a ventilation space is created to allow
           for moisture diffusion. Furring strips that create this venti-
           lation space shall be securely fastened to the stabilization
           members or framing. The cladding shall be fastened to the
           wood furring strips in accordance with the manufacturer’s
           instructions. Insect screening shall be provided at the top
           and bottom of the ventilation space.


                          SECTION AR104
                     THERMAL PERFORMANCE
         AR104.1 Thermal characteristics. Walls with light straw-
         clay infill of densities of greater than or equal to 20 pounds
         per cubic foot (480.6 kg/m ) shall be classified as mass walls
                               3
         in accordance with Section N1102.2.5 (R402.2.5) and shall
         meet  the  R-value  requirements  for  mass  walls  in  Table
         N1102.1.2  (R402.1.2).  Walls  with  light  straw-clay  infill  of
         densities  less  than  20  pounds  per  cubic  foot  (480.6  kg/m )
                                                         3
         shall meet the R-value requirements for wood frame walls in
         Table N1102.1.2 (R402.1.2).
         AR104.2  Thermal  resistance.  Light  straw-clay  shall  be
         deemed  to  have  a  thermal  resistance  as  specified  in  Table
         AR103.2.3.