Page 41 - ICC IEBC 2018
P. 41

REPAIRS



              [BS] 405.2.3.3 Extent of repair for noncompliant   dence of over fusing or tampering per applicable require-
              buildings. If the evaluation does not establish that the  ments of Section 240.51(B) of NFPA 70.
              building in its predamage condition complies with the  406.1.3 Nongrounding-type receptacles. For  replace-
              provisions of Section 405.2.3.1, then the building shall  ment of nongrounding-type receptacles with grounding-
              be retrofitted to comply with the provisions of this sec-  type receptacles and for branch circuits that do not have an
              tion. The wind loads for the repair and retrofit shall be  equipment grounding conductor in the branch circuitry,
              those required by the building code in effect at the time  the grounding conductor of  a grounding-type receptacle
              of original construction, unless the damage was caused  outlet shall be permitted to be grounded to any accessible
              by wind, in which case the wind loads shall be in accor-  point on the grounding electrode system or to any accessi-
              dance with the International Building Code. The seis-  ble point on the grounding electrode conductor in accor-
              mic loads for this retrofit design shall be those required  dance with Section 250.130(C) of NFPA 70.
              by the building code in effect at the time of original
              construction, but not less than the reduced  seismic  406.1.4 Group I-2 receptacles. Receptacles in patient bed
              forces.                                            locations of Group I-2 that are not “hospital grade” shall
                                                                 be replaced with “hospital grade” receptacles, as required
           [BS] 405.2.4 Substantial structural damage to gravity  by NFPA 99 and Article 517 of NFPA 70.
           load-carrying components.  Gravity load-carrying com-
           ponents that have sustained substantial structural damage  406.1.5 Grounding of appliances.  Frames of electric
           shall be rehabilitated to comply with the applicable provi-  ranges, wall-mounted  ovens, counter-mounted  cooking
           sions for dead and live loads in the International Building  units, clothes dryers and outlet or junction boxes that are
           Code. Snow loads shall be considered if the  substantial  part of the existing branch circuit for these appliances shall
           structural damage was caused by or related to snow load  be permitted to be grounded to the grounded circuit con-
           effects. Undamaged  gravity load-carrying components  ductor in accordance with Section 250.140 of NFPA 70.
           that receive  dead, live  or snow loads from  rehabilitated
           components shall also be rehabilitated if required to com-
           ply with the design loads of the rehabilitation design.              SECTION 407
                                                                                 MECHANICAL
              [BS]  405.2.4.1 Lateral force-resisting  elements.
              Regardless of the level of damage to vertical elements  407.1 General. Existing mechanical systems undergoing
              of the lateral  force-resisting  system, if  substantial  repair shall not make the building less complying than it was
              structural damage to gravity load-carrying components  before the damaged occurred.
              was caused primarily by wind or seismic effects, then  407.2 Mechanical draft systems for manually fired appli-
              the building shall be evaluated in accordance with Sec-  ances and  fireplaces. A mechanical draft system  shall be
              tion 405.2.3.1 and, if noncompliant, retrofitted in accor-  permitted to be used with manually fired appliances and fire-
              dance with Section 405.2.3.3.                   places where such a system complies with all of the following
                Exceptions:                                   requirements:
                   1. Buildings assigned to  Seismic Design Cate-  1. The mechanical draft  device  shall be  listed and
                     gory A, B, or C whose substantial structural  installed in accordance with the manufacturer’s instal-
                     damage was not caused by  earthquake need     lation instructions.
                     not be evaluated or retrofitted for load combi-  2. A device shall be installed that  produces visible and
                     nations that include earthquake effects.      audible  warning  upon  failure of the mechanical draft
                   2. One- and two-family dwellings  need  not be  device or loss of electrical power at any time that the
                     evaluated or retrofitted for load combinations  mechanical draft device is turned on. This device shall
                     that include earthquake effects.              be equipped with a battery backup if it receives power
                                                                   from the building wiring.
           [BS] 405.2.5 Flood hazard areas. In flood hazard areas,
           buildings that have sustained substantial damage shall be  3. A smoke detector shall be installed in the room with the
           brought into compliance with Section 1612 of the Interna-  appliance or fireplace. This  device  shall  be equipped
           tional Building Code, or Section R322 of the International  with a battery backup if it receives power from the
           Residential Code, as applicable.                        building wiring.


                           SECTION 406                                          SECTION 408
                            ELECTRICAL                                            PLUMBING
         406.1 Material. Existing electrical wiring and  equipment  408.1 Materials. Plumbing materials and supplies shall not
         undergoing repair shall be allowed to be repaired or replaced  be used for  repairs that are prohibited in the  International
         with like material.                                  Plumbing Code.
           406.1.1 Receptacles. Replacement of electrical recepta-  408.2 Water closet replacement. The maximum water con-
           cles shall comply with the applicable requirements of Sec-  sumption flow rates and quantities for all replaced water clos-
           tion 406.4(D) of NFPA 70.                          ets shall be 1.6 gallons (6 L) per flushing cycle.
           406.1.2 Plug fuses. Plug fuses of the Edison-base type  Exception: Blowout-design water closets [3.5 gallons (13
           shall be used for replacements only where there is no evi-  L) per flushing cycle].                    *

         22                                                             2018 INTERNATIONAL EXISTING BUILDING CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   36   37   38   39   40   41   42   43   44   45   46