STORM DRAINAGE



         1106.2 Size of storm drain piping. Vertical and horizontal             SECTION 1108
         storm drain piping  shall  be sized  based on the flow  rate  SECONDARY (EMERGENCY) ROOF DRAINS
         through the roof drain. The flow rate in storm drain piping  1108.1 Secondary (emergency overflow)  drains or scup-
         shall not exceed that specified in Table 1106.2.     pers. Where roof drains are required, secondary (emergency
         1106.3 Vertical leader sizing. Vertical leaders shall be sized  overflow) roof drains or scuppers shall be provided where the
         based on the flow rate from horizontal gutters or the maxi-  roof perimeter construction extends above the roof in such a
         mum  flow rate  through  roof drains. The flow rate through  manner that water will be entrapped if the primary  drains
         vertical  leaders shall not exceed that  specified in Table  allow buildup for any reason. Where primary and secondary
         1106.3.                                              roof drains are manufactured as a single assembly, the inlet
         1106.4 Vertical walls. In sizing roof drains and storm drain-  and outlet for each drain shall be independent.
         age  piping,  one-half  of  the area of any vertical wall that          TABLE 1106.3
         diverts rainwater to the roof shall be added to the projected      VERTICAL LEADER SIZING
         roof area for inclusion in calculating the required size of ver-
                                                                     SIZE OF LEADER            CAPACITY
         tical conductors, leaders and horizontal storm drainage pip-   (inches)                 (gpm)
         ing.                                                             2                       30
         1106.5 Parapet wall scuppers. Where scuppers are used for      2 × 2                     30
         primary roof drainage or for secondary (emergency overflow)    1   1
         roof drainage or both, the quantity, size, location and inlet  1 /  × 2 / 2              30
                                                                         2
                                                                          1
         elevation of the scuppers shall be chosen to prevent the depth  2 / 2                    54
         of ponding water on the roof from exceeding the maximum       2 /  × 2 /                 54
                                                                            1
                                                                        1
         water depth that the roof was designed for as determined by     2   2
         Section 1611.1 of the International Building Code. Scupper       3                       92
         openings shall be not less than 4 inches (102 mm) in height    2 × 4                     92
         and have a width that is equal to or greater than the circum-  2 /  × 3                  92
                                                                         1
                                                                          2
         ference of a roof drain sized for the same roof area. The flow   4                       192
         through the primary  system shall not be  considered when
                                                                           1
         locating and sizing secondary scuppers.                        3 × 4 / 4                 192
                                                                         1
         1106.6 Size of roof gutters. Horizontal gutters shall be sized  3 /  × 4                 192
                                                                          2
         based on the flow rate from the roof surface. The flow rate in   5                       360
         horizontal gutters  shall not exceed that specified in  Table  4 × 5                     360
         1106.6.
                                                                            1
                                                                        1
                                                                       4 /  × 4 /                 360
                                                                         2   2
                                                                          6                       563
                           SECTION 1107
               SIPHONIC ROOF DRAINAGE SYSTEMS                           5 × 6                     563
                                                                            1
                                                                        1
                                                                       5 /  × 5 /                 563
         1107.1 General. Siphonic roof drains and drainage systems       2   2
         shall be  designed in  accordance  with ASME A112.6.9  and       8                      1208
         ASPE 45.                                                       6 × 8                    1208
                                                              For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m.
                                                       TABLE 1106.2
                                                  STORM DRAIN PIPE SIZING
                                                               CAPACITY (gpm)
              PIPE SIZE                                           SLOPE OF HORIZONTAL DRAIN
              (inches)      VERTICAL DRAIN
                                              1                 1                1                1
                                              / 16  inch per foot  / 8  inch per foot  / 4  inch per foot  / 2  inch per foot
                 2               34               15                22               31               44
                 3               87               39                55               79               111
                 4              180               81               115               163              231
                 5              311               117              165               234              331
                 6              538               243              344               487              689
                 8              1,117             505              714              1,010            1,429
                10              2,050             927              1,311            1,855            2,623
                12              3,272            1,480             2,093            2,960            4,187
                15              5,543            2,508             3,546            5,016            7,093
         For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.


         94                                                                     2018 INTERNATIONAL PLUMBING CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.