P. 37

GENERAL REGULATIONS



         instructions. Thermal expansion tanks shall not be supported           SECTION 309
         by the piping that connects to such tanks.                     FLOOD HAZARD RESISTANCE
                             TABLE 308.5                      309.1 General. Plumbing systems  and equipment in struc-
                          HANGER SPACING                      tures erected in  flood hazard  areas shall be constructed  in
                                   MAXIMUM      MAXIMUM       accordance with the requirements of this  section and the
              PIPING MATERIAL     HORIZONTAL    VERTICAL      International Building Code.
                                 SPACING (feet)  SPACING (feet)
         Acrylonitrile butadiene                    b         [BS] 309.2 Flood hazard. For structures located in flood haz-
                                      4           10
           styrene (ABS) pipe                                 ard areas,  the following  systems  and equipment shall be
                                                              located and installed as required by Section 1612 of the Inter-
         Aluminum tubing             10            15
                                                              national Building Code.
         Brass pipe                  10            10
         Cast-iron pipe               5 a          15            1. Water service pipes.
         Chlorinated polyvinyl chloride                          2. Pump seals in individual water supply systems where
           (CPVC) pipe and tubing, 1   3          10 b             the pump is located below the design flood elevation.
           inch and smaller
                                                                 3. Covers on potable water wells shall be sealed, except
         Chlorinated polyvinyl chloride                            where the top of the casing well or pipe sleeve is ele-
                              1
           (CPVC) pipe and tubing, 1 /  4         10 b             vated to not less than 1 foot (305 mm) above the design
                               4
           inches and larger                                       flood elevation.
         Copper or copper-alloy pipe  12           10
                                                                 4. Sanitary drainage piping.
         Copper or copper-alloy tubing,
            1
           1 / -inch diameter and     6            10            5. Storm drainage piping.
             4
           smaller                                               6. Manhole covers shall be sealed, except where elevated
                                                                   to or above the design flood elevation.
         Copper or copper-alloy tubing,
            1
           1 / -inch diameter and larger   10      10            7. Other plumbing fixtures, faucets, fixture fittings, piping
             2
         Cross-linked polyethylene                                 systems and equipment.
                                     2.67
             (PEX) pipe 1 inch and                10 b
                                  (32 inches)                    8. Water heaters.
           smaller
                                                                 9. Vents and vent systems.
         Cross-linked polyethylene
                    1
           (PEX) pipe 1 /  inch and   4           10 b           Exception: The systems listed in this section are permitted
                     4
           larger                                                to be located below the elevation required by Section 1612
                                                                 of the International Building Code for utilities and atten-
         Cross-linked polyethylene/
                                                                 dant  equipment,  provided that the  systems are designed
           aluminum/cross-linked     2.67
           polyethylene (PEX-AL-  (32 inches)      4             and installed to prevent water from entering or accumulat-
                                                                 ing  within  their components and  the systems are  con-
           PEX) pipe
                                                                 structed to resist hydrostatic and hydrodynamic loads and
         Lead pipe                Continuous       4
                                                                 stresses, including the effects  of buoyancy, during  the
         Polyethylene/aluminum/
                                     2.67                        occurrence of flooding up to such elevation.
           polyethylene (PE-AL-PE)                 4
                                  (32 inches)
            pipe                                              [BS] 309.3 Coastal high-hazard areas and coastal A zones.
                                                              Structures located in coastal high-hazard areas and coastal A
         Polyethylene of raised
                                     2.67                     zones shall meet the  requirements  of  Section 309.2.  The
           temperature (PE-RT) pipe 1             10 b
                                   (32 inches)                plumbing systems, pipes and fixtures shall not be mounted on
           inch and smaller
                                                              or penetrate through walls intended to break away under
         Polyethylene of raised                               flood loads.
           temperature (PE-RT) pipe   4           10 b
            1
           1 /  inch and larger
             4
         Polypropylene (PP) pipe or  2.67           b                           SECTION 310
            tubing 1 inch and smaller   (32 inches)  10        WASHROOM AND TOILET ROOM REQUIREMENTS
         Polypropylene (PP) pipe or                 b         310.1 Light and ventilation. Washrooms and toilet rooms
                 1
           tubing, 1 / inches and larger  4       10
                  4                                           shall  be illuminated and ventilated in accordance with the
         Polyvinyl chloride (PVC) pipe   4        10 b        International Building Code  and International  Mechanical
         Stainless steel drainage                             Code.
                                     10           10 b
           systems
                                                              310.2 Location of fixtures and compartments. The location
         Steel pipe                  12            15         of plumbing fixtures and the requirements for compartments
         For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.         and partitions shall be in accordance with Section 405.3.
         a. The maximum  horizontal  spacing  of  cast-iron pipe hangers shall be
           increased to 10 feet where 10-foot lengths of pipe are installed.  310.3 Interior finish. Interior finish surfaces of toilet rooms
         b. For sizes 2 inches and smaller, a guide shall be installed midway between  shall comply with the International Building Code.
           required vertical supports. Such guides shall prevent pipe movement in a
           direction perpendicular to the axis of the pipe.