Acousti-Seal  933E Technical Data
                                ®
               10 22 26 (10650) Operable Partitions



               ACOUSTI-SEAL  900 SERIES TECHNICAL DATA
                                    ®

               1.5 DELIVERY, STORAGE, AND HANDLING             2.3 PANEL CONSTRUCTION
               A.  Clearly mark packages and panels with       A.  Nominal 3-inch (76 mm) thick panels in
                  numbering systems used on Shop Drawings. Do     manufacturer’s standard 48-inch (1220 mm) widths.
                  not use permanent markings on panels.           All panel horizontal and vertical framing members
               B.  Protect panels during delivery, storage, and   fabricated from minimum 18-gage or 16-gage
                 handling to comply with manufacturer’s direction   formed steel with overlapped and welded corners
                 and as required to prevent damage.               for rigidity. Top channel is reinforced to support
                                                                  suspension system components. Frame is designed
               1.6 WARRANTY                                       so that full vertical edges of panels are of formed
               A.  Provide written warranty by manufacturer of    steel and provide concealed protection of the
                  operable partitions agreeing to repair or replace   edges of the panel skin.
                  any components with manufacturing defects.   B. Panel Skin Options:
               B.  Warranty period: Two (2) years.                1.  1/2-inch (13 mm) NAUF medium density
                                                                    fiberboard, single material or composite
               PART 2 – PRODUCTS                                    layers continuously bonded to panel
                                                                    frame. Acoustical ratings of panels with this
               2.1 MANUFACTURERS, PRODUCTS, AND OPERATION           construction (select one):
               A.  Manufacturers: Subject to compliance with           a. 41 STC
                  requirements, provide product by the following:        b. 47 STC
                  1. Modernfold, Inc.                                  c. 50 STC
               B. Products: Subject to compliance with the        2.  Roll-formed steel wrapping around the panel
                  requirements, provide the following product:      edge. Panel skins shall be lockformed and
                   1. Acousti-Seal #933E electrically operated      welded directly to the frame for unitized
                    continuously hinged operable partition.         construction. Acoustical ratings of panels with
                                                                    this construction (select one):
               2.2 OPERATION                                           a. 28 STC
               A.  Acousti-Seal  #933E: Series of continuously hinged         b. 45 STC
                            ®
                  flat panels, electrically operated, top supported         c. 50 STC
                  with operable floor seals.                           d. 52 STC
               B.  Partition shall be operated by two push button   C.  Hinges for Panels, Closure Panels, Pass Doors, and
                 control stations wired in series and located on   Pocket Doors shall be (select one):
                 opposite sides and opposite ends of the partition.      1.  Full leaf butt hinges, attached directly to panel
                 Control stations shall be activated by key switch   frame with welded hinge anchor plates within
                 at stack end of partition. Motor unit shall be     panel to further support hinge mounting to
                 reversible, continuous duty, and class A insulated.   frame. Lifetime warranty on hinges. Hinges
                 Motor unit shall have NEMA MG 1 service factor,    mounted into panel edge or vertical astragal
                 high starting torque, thermal overload protection,   are not acceptable.
                 and open/drip proof enclosure. Motor assembly      2.  SOSS  Invisible laminated hinge with antifriction
                                                                        ®
                 shall have wiring compliant with NFPA 70, 24 volt   segments mounted between each heat
                 controls, compliant with UL 508A, and speed        treated link. Hinge to be attached directly
                 of 28 feet/minute. The drive unit motor shall be   to panel frame. Welded internal hinge
                 equipped with outboard limit switches to prevent   bracket shall support the hinge and allow for
                 over-extension. A positive chain drive attached    adjustment of hinge plates. Concealed hinges
                 to the lead panel shall pull the partition across the   mounted into edge or vertical astragal are not
                 opening. Cable, belt, or other friction type drives   acceptable.
                 will not be accepted.                         D.  Panel Trim: No vertical trim required or allowed on
               C. Electric motor shall be (select one):           edges of panels; minimal groove appearance at
                  1. 115-volt, 1-phase, 1 HP, 14.0 FLA            panel joints.
                  2. 208/230-volt, 1-phase, 1 HP, 7.0 FLA      E. Panel Weights:
                  3. 208/230-volt, 3-phase, 1 HP, 4.5 FLA         1. Non-Steel Skin
                  4. 460-volt, 3-phase, 1 HP, 2.0 FLA                  a. 41 STC - 6.5 lbs./square foot
                  5. 208/230-volt, 3-phase, 1-1/2 HP, 5.2 FLA          b. 47 STC - 7 lbs./square foot
                                                                       c. 50 STC - 8 lbs./square foot