Page 37 - M1-12 Ops Manual McMurdo 2016
P. 37
r1 =Input Type and Range Value
r2 = Decimal Point Position
0= TCJ
1= TCK
2= TCT
3= TCE
4= TCN
5= TCS
6= TCR
7= TCB
8= TCL
9= TCU
10= TCG
11= TCD
12= TCC
13= TC Plat. II
14= RTD Pt 100
15= Linear
From -100 to From -100 to From -200 to From -100 to From -100 to From -50 to From -50 to From 0 to From -100 to From -200 to From 0 to From 0 to From 0 to From -100 to From -200 to From 0 to From 12 to From 0 to From 4 to From 0 to From 1 to From 0 to From 2 to From -150 to From -150 to From -330 to From -150 to From -150 to
(Available only for linear range r1 = 15 to 22) ____. =Nodecimal
1000 °C 1370 °C 400 °C 800 °C 1400 °C 1760 °C 1760 °C 1820 °C 900 °C 600 °C 2300 °C 2300 °C 2300 °C 1400 °C 850 °C 60 mV 60 mV 20 mA 20 mA 5 V 5 V 10 V 10 V 1830 °F 2500 °F 750 °F 1470 °F 2550 °F 28=TCS From-60to3200°F
___._ =Onedecimalfigure __.__ =Twodecimalfigures _ . _ _ _ = Three decimal figures
16= Linear
17= Linear
18= Linear
19= Linear
20= Linear
21= Linear
22= Linear
r5 = Offset Adjustment
23= TC
24= TC
25= TC
26= TC
27= TC
J K T E N
r6 = Time constant of the filter applied to the displayed value
29= 30= 31= 32= 33= 34= 35= 36 = 37=
TCR From TCB From TCL From TCU From TCG From TCD From TCC From TC Plat. II From RTD Pt100 From
-60 to 3200 °F 32 to 3300 °F -150 to 1650 °F -330 to 1110 °F 0 to 4170 °F 0 to 4170 °F 0 to 4170 °F -150 to 2550 °F -330 to 1560 °F
r7 = Alarm action on input fault.
10
r3 = Initial value of the readout scale
(Available only for linear range r1 = 15 to 22) Range: From -1999 to 9999
r4 = final value of the readout scale
(Available only for linear range r1 = 15 to 22) Range: From -1999 to 9999
Range: From -500 to 500
Offset value algebraically added to the measured value.
Range: From 0 (filter OFF) to 8 seconds. (First order filter with selected time constant.)
When the instrument detects an input failure condition, the alarm will operate as in presence of:
uP = as in presence of the full scale value. doun = as in presence of the initial scale value.