Page 39 - M1-12 Ops Manual McMurdo 2016
P. 39
Example1- C1=HiandC2=O
C4= Shutdown memory
HS (Limiter
Su (Limiter threshold)
0= The shutdown condition will be saved (at next power up it will be reactivated)
Hysteresis)
1= The shutdown condition will be lost in case of power down
ON Relay OUT 1
ON “Reset” LED
C5 = Time Constant of the Filter applied to the Measured Value for Limit Action.
OFF
OFF
Range: From 0 (filter OFF) to 8 seconds Note: First order filter with selected time
Flash Upper display
FLASH
FLASH
Constant.
Steady
A, B, C = Acknowledgment actions. NOTE: Acknowledgment B has no effect.
P1 = Alarm Function
Example2- C1=HiandC2=1
Not provided Process alarm Band alarm Deviation alarm
HS (Limiter
Su (Limiter threshold)
Hysteresis) ON
Relay OUT 1 OFF
P2 = Alarm configuration
ON “Reset” LED
FLASH
FLASH
(Skipped if option is not available or P1 = none) H.A. = High alarm with automatic reset
L.A. = Low alarm with automatic reset
H.A.Ac = High alarm with automatic reset and
OFF
Flash Upper display
FLASH
FLASH
"Silence" function.
L.A.Ac =Low alarm with automatic reset and
Steady
A, B = Acknowledgment actions.
H.L. = L.L. =
"Silence" function.
High alarm with manual reset Low alarm with manual reset
C3 = Rearm at Power-up
Auto = Automatic rearm
nAn = Manual rearm
12
(Skipped when the option is not available)
nonE =
AL.P =
AL.b =
AL.d =
When C1 = Hi.Lo, “AL.b” and “AL.d” are not available.