Page 2 - Safety Rep. Support
P. 2
Final Exit Doors
9 1 Hinges, are at least 3 certified
metal hinges fitted?
Fire doors must be signed, “Press Panic
2
Bar or Pad”
3 7
Labels or plastic pins in the door stile
3 showing that they are fire doors
1 (FD30, FD60)?
5
Are external fire door seals completely
4 fitted around in the rebate of the door and
do they fit properly?
5 5 Does the panic bar open and close
properly and does the locking bar engage
fully?
8 The maximum gap between the door and
6 6 frame must not exceed 4 mm. Does the
door open and close properly in the
rebate?
4
5
Does the door closer close the door fully
7
and into the rebate properly?
2 PUSH TO OPEN
Rebate The door should open in the direction
8
of travel?
Final exit doors can stay open for
ventilation.
9