IGEM NEWS | Young Persons Paper Competition 2017

                 SMART RISER JACKET






                 By Raymond Mung Yuen Wai, Assistant Engineer at the Hong Kong
                 and China Gas Company Limited and YPPC 2017 finalist


                      n Hong Kong, a typical gas riser
                      system consists of a base support,   TABLE 1: Standard riser repair methods
                      the service main riser and the
                      service lateral, providing a reliable   Methods   Anti-corrosion tape  Gas pipe leakage sealant
                      and safe gas supply to customers.
                 ISome risers can become
                 corroded due to prolonged exposure   Gas pressure availability  LPA-LPB     LPA
                 to corrosive chemicals, mostly   Curing time           Instantly            24 hours
                 occurring in aging buildings.    Required gas suspension  No                Yes
                 According to government statistics
                 from 2016, the number of buildings   Durability        Temporary repair     Permanent repair
                 aged 30 years or more exceeds 21,000,   Advantages     Quick fix for emergency   Stops gas leaks
                 and this number is increasing                          use only             permanently

                                                  Limitations           Trapped moisture can   Only can be used on
                 FIGURE 1: A typical riser system                       aggravate corrosion  thread gas leakage and
                                                                                             has a long curing time


                                                  considerably every year. The number of
                                                  riser replacements is also expected to   FIGURE 3: Bending at the branch section
                                                  increase as more buildings age. Cost,
                                                  manpower and time are considerable
                                                  and critical factors in implementing
                                                  riser replacement.
                                                    Despite their suitability in certain
                                                  scenarios, the limitations of the usual
                                                  riser repair methods can constrain
                                                  their implementation in real life. In
                                                  that case, replacement of the
                                                  corroded riser becomes the only
                                                  solution to ensure a safe gas supply.
                                                  However, replacement, too, has its
                                                  drawbacks.

                                                  DOWNSIDES OF RISER
                                                  REPLACEMENT
                 FIGURE 2: Replaced riser         Temporary gas suspension
                                                  To ensure a safe and reliable gas   Material wastage
                                                  supply, replacement of the riser is   The replacement of service risers
                                                  often unavoidable. However, it requires   produces surplus material such as
                                                  interruption of the gas supply, causing   extra pipe segments and couplings.
                                                  an inconvenience to users. In addition,   For example, replacing a 0.3m
                                                  one week's advance notice is required   defective section on a 3m service main
                                                  to inform gas users. This period   riser means removing the whole 3m
                                                  between the notice being issued and   section to ensure the remaining
                                                  the riser replacement poses a potential   pipelines are not contaminated. Ninety
                                                  safety risk.                     per cent of materials are wasted in
                                                                                   order to recover a relatively small
                                                  Lateral service corrosion        area. This is not a very
                                                  Removal of the main riser may induce a   environmentally friendly approach.
                                                  downward pulling force on the lateral
                                                  service risers, which may become bent or   SMART RISER JACKET
                                                  twisted. The bending stress can cause   In order to avoid the typical pitfalls and
                                                  cracking at the backfill, trapping   constraints of replacing defective risers,
                                                  rainwater and sewage and accelerating   a new method called the Smart Riser
                                                  corrosion to the service lateral.  Jacket has been invented.