Operable Partitions
10 22 26 (10650) PART 1 - MODEL 2030 GENERAL SPECIFICATION
1.01 WORK INCLUDED E. ASTM A 653: Specifi cation for General Requirements for Steel
A. Operable Wall System shall be furnished, installed and serviced by Sheet, Alloy-Coated (Galvanneal) by the Hot Dip Process.
KWIK-WALL's authorized distributor, in compliance with the F. ASTM C 423: Standard Test Method for Sound Absorption and
architectural drawings and specifi cations contained herein. Sound Absorption Coeffi cients by the Reverberation Room
Method.
1.02 RELATED WORK G. CCC-W-408A: Federal Specifi cation which applies to Vinyl
Coated Wall Coverings.
A. Structural Support: Structural support system required for H. CFFA-W-101-D: Chemical Fabrics and Film Association
suspending the operable wall shall be designed, installed and Quality Standard for Vinyl Coated Fabric Wall Coverings
pre-punched by others, in accordance with ASTM E 557 and
KWIK-WALL's shop drawings.
1.06 SUBMITTALS
B. Insulation: Sound insulation and baffl es for the plenum area above
the track system, under the permanent fl oor, inside air ducts A. KWIK-WALL shall provide written technical information and
passing over or around the operable wall, and in permanent walls related detail drawings, which demonstrate that the products
adjoining the operable wall system shall be by others, in comply with contract documents for each type of operable
accordance with ASTM E 557. partition specifi ed.
B. KWIK-WALL shall provide detailed engineering drawings
C. Opening Preparation: Proper and complete preparation of the featuring track plan, panel elevation, horizontal and vertical
operable wall system opening shall be by others in accordance with details and beam punching template as required.
ASTM E 557, and shall include fl oor leveling; plumbness of C. KWIK-WALL shall provide written test report of the independent
adjoining permanent walls; substrate and or ceiling tile enclosures acoustical testing laboratory certifying the attainment of the
for the track system; and the painting and fi nishing of trim and specifi ed STC rating, upon request.
other materials adjoining the head and jamb areas of the operable D. KWIK-WALL shall provide written instructions specifying the
wall. Any permanent wall(s) receiving an adjustable or fi xed wall proper operation and maintenance of the operable wall system.
jamb will require internal structural blocking in order to secure the E. KWIK-WALL shall provide a color selector demonstrating the
jamb to the permanent wall. Refer to a copy of the shop drawings manufacturer's selections of the specifi ed fi nish material. Samples
for additional details. shall consist of actual swatches of the specifi ed fi nish material.
1.03 SYSTEM DESCRIPTION
1.07 DELIVERY, STORAGE AND HANDLING
A. The operable wall system shall consist of Hinged Pair Panels that
are top supported by one (1) carrier. Featuring panels hinged A. Panels shall be individually wrapped in a protective plastic
together in evenly matched pairs (groups of two (2)), unless covering to keep panels clean during delivery, storage and
otherwise specifi ed. handling.
B. Panels shall be stored on edge and above the fl oor on cushioned
B. The operable wall system shall consist of acoustically rated panels blocking in a dry and ventilated area, protected from humidity and
tested in accordance with ASTM E 90 and ASTM E 413 test temperature extremes.
procedures, and shall have achieved a STC rating as specifi ed
herein (see "Acoustical Performance" article listed under 1.08 SEQUENCING / SCHEDULING
Part 2 - Products).
A. Beam Punching: KWIK-WALL shall provide beam punching
1.04 QUALITY ASSURANCE template drawing detailing the anchor locations for the suspended
track system (as required for Drop Rod Mounting), as required for
A. The operable wall shall have been tested in an independent the fabrication and installation of structural overhead support
acoustical testing laboratory in accordance with ASTM E 90 and
ASTM E 413 test procedures. by others.
B. Track Installation: Scheduling of operable wall track installation
B. The operable wall panel construction and fi nish materials shall shall occur after structural overhead support has been properly
consist of Class A rated materials (except as noted, under and completely fabricated and installed by others.
“Finishes” Part 2 – Products) in accordance with ASTM E 84. C. Panel Installation: Operable wall panel installation shall occur
C. The operable wall shall be installed by KWIK-WALL's after fi xed wall substrate construction is properly and completely
authorized distributor in accordance with ASTM E 557. installed by others, as required to protect panels from ongoing
adjacent construction.
1.05 REFERENCES
A. ASTM E 90: Laboratory Measurement of Airborne-Sound 1.09 WARRANTY
Transmission Loss of Building Partitions. A. KWIK-WALL shall warrant each partition and its component
B. ASTM E 413: Determination of Sound Transmission Class (STC). parts to be free from defects in material and workmanship for a
C. ASTM E 557: Architectural Application and Installation of period of fi ve (5) years from the date of delivery to the original
Operable Partitions. purchaser, when installed by an authorized KWIK-WALL distributor
D. ASTM E 84: Surface Burning Characteristics of Building (see actual warranty on Page 12 for details and limitations).
Materials.
2
Dimensions in [ ] are millimeters. Contact your local distributor for additional assistance or visit www.kwik-wall.com 12-16