Planning Instruction 66571760GB0 Fire Detection 4
Example 3: FX 3NET communication segments, long distances
S1
Segment 0 S2 Max. 1000 m
C C
FX_ FX_
M M
Max. 5 km *)
M M
FX_ FX_ C C FX_
S1
Root
Segment 1 S2 Max. 1000 m
C C C C
M M M M
M M
C C FX_ FX_
S1
Segment 2 S2 Max. 1000 m
FX_
Modem Link
Max. 5 km *)
M M
FX_ FX_ C C FX_
S1
Segment n S2 Max. 1000 m
C = CODINET (Modem Adaptor)
M = Modem
Modem Link = 2 x Modems + 2 x CODINET
Note! Maximum number of Modem Links in series between 2 FX_ panels is 2.
© 2009 Schneider Electric. All rights reserved.
Note! Also Modem Links must be doubled.
*) According to modem specification
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic