Specifications

                                             Catalog Number       GSA-M270         GSA-M270P,        GSA-M278
                                                                  Single Action   Single Action -Two   Double Action
                                             Description
                                                                  - One Stage     Stage (Presignal)  - One Stage
         Technology that saves lives         Addressing          Uses 1 Module    Uses 2 Module     Uses 1 Module
                                             Requirements          Address          Addresses         Address
         Contact us...                       Operating Current  Standby = 250µA   Standby = 396µA   Standby = 250µA
         Email: kidde.fire@fs.utc.com                           Activated = 400µA  Activated = 680µA  Activated = 400µA
         Web:   Kidde.com/EngineeredSystems                           Diecast Zinc - Red Epoxy     Lexan - Red with
                                             Construction & Finish
                                                                      with aluminum markings        white markings
         Kidde is a UTC brand.               Type Code                             Factory Set
         1016 Corporate Park Drive           Operating Voltage             15.2 to 19.95 Vdc (19 Vdc nominal)
         Mebane, NC 27302                                             Operating Temperature: 32ºF to 120ºF (0ºC to 49ºC)
                                             Storage and Operating   Storage Temperature: -4ºF to 140ºF (-20ºC to 60ºC) Humidity: 0 to 93%
         © 2016 United Technologies Corporation.   Environment                        RH
         All rights reserved.                                           On-board Green LED - Flashes when polled
                                             LED Operation
                                                                        On-board Red LED - Flashes w hen in alarm
                                             Compatibility                 Use With: Signature Loop Controller
                                             Agency Listings                  UL, ULC, MEA, CSFM, FM


                                            Ordering Information

                                                                                                          Ship
                                             Catalog                                                      Wt. lbs
                                             Number     Description                                       (kg)
                                                        One Stage Fire Alarm Station,  English Markings
                                             GSA-M270
                                                        - UL/ULC Listed
                                                        Two Stage (Presignal) Fire Alarm Station, English Markings
                                             GSA-M270P                                                    1 (0.5)
                                                        - UL/ULC Listed
                                                        Double Action (One Stage) Fire Alarm Station, English Markings
                                             GSA-M278
                                                        - UL/ULC Listed
                                             Accessories
                                             270-GLR    20 Glass Rods - for GSA-M270 series  (USA ONLY)
                                             276-GLR    20 Glass Rods - for GSA-M278 series