Page 39 - Fire Alarm-Submittal
P. 39

KIDDE  Catalog u Intelligent Input-Output
                                                                                            ®



                                                                                        Compatible with VS & VM control systems
           Technology that saves lives




           Input Modules


           GSA-CT1, GSA-CT1HT,

           GSA-CT2, GSA-MCT2







                                                                                                               7300-1483:
                                                                                                                 0115
                                                                                                GSA-CT1/2

                                                             GSA-MCT2
                                                                                                                S3424

           Overview                                              Standard Features

           The GSA-CT1 Single Input Module, GSA-CT1HT High       •  Multiple applications
           Temperature Single Input Module and GSA-CT2/GSA-MCT2 Dual   Including Alarm, Alarm with delayed latching (retard) for
           Input Modules are intelligent analog addressable devices used to   waterflow applications, Supervisory, and Monitor. The installer
           connect one or two Class B normally-open Alarm, Supervisory, or   selects one of four “personality codes” to be downloaded to
           Monitor type dry contact Initiating Device Circuits (IDC).  the module through the loop controller.
           The actual function of these modules is determined by the   •  GSA-CT1HT rated for high temperature environments
           “personality code” selected by the installer. This code is downloaded   Suitable for attic installation and monitoring high temperature
           to the module from the Signature loop controller during system   heat detectors.
           configuration.                                        •  Plug-in (UIO) or standard 1-gang mount
                                                                    UIO versions allow quick installation where multiple modules
           The input modules gather analog information from the initiating   are required. The 1-gang mount version is ideal for remote
           devices connected to them and convert it into digital signals.   locations that require a single module.
           The module’s on-board microprocessor analyzes the signal and
           decides whether or not to input an alarm.             •  Automatic device mapping
                                                                    Signature modules transmit information to the loop controller
           The GSA-CT1, GSA-CT1HT and GSA-CT2 mount to standard     regarding their circuit locations with respect to other Signature
           North American 1-gang electrical boxes, making them ideal for   devices on the wire loop.
           locations where only one module is required. Separate I/O and   •  Electronic addressing
           data loop connections are made to each module.           Programmable addresses are downloaded from the loop
           The GSA-CT1HT module operates at an expanded temperature   controller, a PC, or the Signature Program/Service Tool.
           range of 32 ºF to 158 ºF (0 ºC  to 70 ºC) for those applications   There are no switches or dials to set.
           requiring more extreme environmental temperature variation.  •  Ground fault detection by address
           The GSA-MCT2 is part of the UIO family of plug-in Signature   Detects ground faults right down to the device level.
           Series modules. It functions identically to the GSA-CT2, but
           takes advantage of the modular flexibility and easy installation
           that characterizes all UIO modules. Two- and six-module UIO
           motherboards are available. All wiring connections are made to
           terminal blocks on the motherboard. UIO assemblies may be
           mounted in Kidde enclosures.






           Page 1 of 4                                                                  DA T A SHEET  K85001-0241
                                                                                Not to be used for installation purposes.  Issue 1.1
  03-27-20
   34   35   36   37   38   39   40   41   42   43   44