Page 29 - Simplified Wastewater Treatment Fundementals\Package Plants
P. 29

Package Plants





                                 Detention Time



                                 The rectangular chlorine contact chamber is 10 feet long, 15 feet wide and 10 feet

                                 deep. If the flow rate in to the chlorine contact chamber is 1.0 MGD, what is the

                                 detention time?


                                 Formula Needed



                                 Length x Width x Depth x 7.48 cubic feet/gallons


                                 10 x 15 x 10 x 7.48 = 11,220 gallons


                                 Volume MG x 24 Hours =      Detention Time in Hours



                                          Flow MGD


                                 0.0112 MG x 24 Hours = 0.26 Hours



                                           1.0 MGD


                                 Is the Chlorine Contact Chamber providing at least 90 minutes of contact time?


                                 Answer – No
   24   25   26   27   28   29   30   31   32