20. Fire water
sprinkler system.
a. A drain of minimum 2” size has to be provided outside the dyke near the isolation valve to prevent water to
sprinklers in case of valve passing and drain the accumulated water after testing.
Action: Maint- Field (Offsite)/ F&S / OM&S Target: 31st December -2021.
b. Metallurgy upgradation shall be explored to suit CPCL fire water quality.
Action: Inspection Target: 31 August -2021.