Page 21 - TTS Product Sheet 2023
P. 21
Specifications
General Cooling Systems
Weight Cooling Capacity
12.00 lb (5.44 kg) 1200W (4095BTU/hr) @ 25°C liquid-
Fitting Thread ambient (25°C dT)
NPT 1/4 Display Type
Max Pressure Tolerance OLED
@ 25°C Max Flow Rate (10-13mm ID)
5.0LPM (1.3GPM)
2kgf/cm2 (28.5psi) Max Power Consumption
Max Temperature Tolerance 97W
60°C (140°F) Max Static Pressure (10-13mm ID)
Noise (dBA) 0.4kgf/cm2 (6psi)
30-63 Power Source
Dimensions 12 VDC
650x185x130mm Radiator
Brass/Copper, 3 x 120mm fans
Temperature Sensors
Liquid & Two K-Type Thermocouples
(optional)
Temperature Stability
+/-0.5ºC
60
55
50
10% Percentage Error Line
Tc (°C) 45 Lab Test
40 Simulation TIM RS
Simulation No TIM RS
35
30
400 600 800 1000 1200 1400
Power (W)
Tc Versus Power For SQ80 Water Block (4 Heaters)
Temperature (Fluid): 38.68°C Temperature (Fluid): 33.33°C
Hand Socket Lid Note: Power 1219W
Temperature Contours For SQ80 Water Block
www.tts-grp.com
@ 2021, Test Tooling Solutions Group. All rights reserved.