•  No more than 50 litres for extremely or highly flammable liquids; and
               •  No more than 250 litres for other flammable liquids.

               Safe use of flammable liquids includes the following:

               •  Use the minimum volume of liquid required.
               •  Store the liquid in a properly labeled container.
               •  Ideally, ensure that the container is metal with a self-closing lid.
               •  Use a metal tray to catch spills and have absorbent materials available.
               •  Use away from heat and ignition sources.
               •  Ensure that workspace is well-ventilated.
               •  Return containers to safe storage after use.

               Safe storage of small volumes (extremely/highly flammable (<50 litres) or flammable (<250 litres)) in
               workrooms includes:

               •  Storing minimal volumes only.
               •  Using closed containers.
               •  Storing in a purpose-built flammable cabinet. A flammables cabinet should: –– Be fire-resistant
                 (metal).
               •  Have lockable doors and fire-resistant hinges and fastenings. –– Be clearly signed.
               •  Have a built-in catch tray.
               •  Storing away from potential ignition sources.


               Safe storage of larger volumes of flammable liquid involves:
               •  Storing flammables in a purpose-built, single-storey flammables store, with segregated storage if
                 necessary.
               •  The store being built of non-combustible materials.
               •  The store having a lightweight roof for explosion relief.
               •  Ideally, the store being built outdoors away from other buildings or having firewall protection.
               •  The store being suitably fenced in a secure area.
               •  All electrical systems being intrinsically safe.
               •  All other ignition sources being eliminated.
               •  The store being well-ventilated at high and low levels.
               •  All access doors being lockable with a sill to contain spillages.
               •  Having adequate fire-fighting equipment.
               •  Making regular checks for security, secure and safe storage, leaks of liquids, etc.