Page 141 - Programmable Logic Controllers, Fifth Edition
P. 141

3. Package moves to the position of the limit switch
                                                                        Figure 6-64 shows an I/O connection diagram for a
                    and automatically stops.                         programmed version of the sequential process. Each input
                                                                     and output device is represented by its symbol and asso-
               Other auxiliary features include:
                                                                     ciated address. These addresses will indicate what PLC
                 •  a stop button that will stop the table, for any reason,   input is connected to what input device and what PLC
                    before the package reaches the limit switch position;  output will drive what output device. The address code, of
                 •  a red pilot light to indicate the table is stopped; and  course, will depend on the PLC model used. This example
                 •  a green pilot light to indicate the table is running.  uses SLC 500 addressing for the process. Note that the
                                                                     electromagnetic control relay CR is not needed because
                  A relay schematic for the sequential process is shown   its function is replaced by an internal PLC control relay.
               in Figure 6-63. The operation of this hardwired circuit can   The hardwired relay schematic for the sequential pro-
               be summarized as follows:                             cess can be converted to the PLC ladder logic program

                 •  Start button is actuated; CR is energized if stop but-  shown in Figure 6-65. In converting the process to a pro-
                    ton and limit switch are not actuated.           gram the operation of each rung must be understood. The
                 •  Contact CR-1 closes, sealing in CR when the start   pushbuttons PB1, PB2 as well as limit switch LS are all
                    button is released.                              programmed using the examine-closed (–] [–) instruction
                 •  Contact CR-2 opens, switching the red pilot light   to produce the desired logic control. Also, internal relay
                    from on to off.                                  B3:1/0 is used to replace control relay CR. To obtain the
                                                                     desired control logic, all internal relay contacts are pro-
                 •  Contact CR-3 closes, switching the green pilot light   grammed using the PLC contact instruction that matches
                    from off to on.                                  the coil de-energized state.  The internal relay imple-
                 •  Contact CR-4 closes to energize the motor starter   mented in software requires one coil address the contacts
                    coil, starting the motor and moving the package to-  of which can be examined for an ON or OFF condition as
                    ward the limit switch.                           many times as you like.
                 •  Limit switch is actuated, de-energizing relay       There is more than one method to correctly design the
                    coil CR.                                         ladder logic program for a given control process. In some
                 •  Contact CR-1 opens, opening the seal-in circuit.  cases one arrangement may be more efficient in terms of
                 •  Contact CR-2 closes, switching the red pilot light   the amount of memory used and the time required to scan
                    from off to on.                                  the program. Figure 6-66 illustrates an example of an ar-
                 •  Contact CR-3 opens, switching the green pilot light   rangement of series instructions of a rung programmed
                    from on to off.                                  for optimum scan time. The series instructions are pro-
                 •  Contact CR-4 opens, de-energizing the motor starter   grammed  from  the  most  likely  to be  false  (far  left)  to
                                                                     the least likely to be false (far right). Once the processor
                    coil to stop the motor and end the sequence.
                                                                     sees a false input instruction in series, the processor stops
                                                                     checking the rung at the false condition and sets the out-
                                                                     put false.
                     L1                                    L2
                         PB1                LS                          Figure 6-67 illustrates an example of an arrangement
                        Start     PB2      Limit   Control           of parallel instructions of a rung programmed for opti-
                                  Stop     switch  relay
                                                                     mum scan time. The parallel path that is most often true is
                                                    CR

                                                                              Inputs                     Outputs
                        CR-1                        PL1              L1                    L2   L1                    L2
                                                    Stop                                                    Motor starter
                                                     R                   PB1 - Start                           coil
                        CR-2                                                                         O:4/1     M
                                                    PL2                              I:3/0
                                                    Run                                                      PL1 - Stop
                                                                         PB1 - Stop
                                                     G                                               O:4/2      R
                        CR-3                 Motor                                   I:3/1
                                           starter coil                                                      PL2 - Run
                                                                       LS - Limit switch
                                              M                                      I:3/2           O:4/3      G
                        CR-4                           OL
               Figure 6-63  Relay schematic for the sequential process.   Figure 6-64  I/O connection diagram.



               122        Chapter 6  Developing Fundamental PLC Wiring Diagrams and Ladder Logic Programs







          pet73842_ch06_098-130.indd   122                                                                              05/11/15   4:20 PM
   136   137   138   139   140   141   142   143   144   145   146