L1   Inputs         T4:6      Ladder logic program                       Output  L2
                                                               TON
                                                               TIMER ON DELAY         EN
                                                DN             Timer           T4:5   DN
                                    FS                         Time base        1.0           Light
                                                               Preset             1
                                                               Accumulated       0
                                              T4:5
                                                               TON
                                                               TIMER ON DELAY         EN
                                                DN             Timer           T4:6   DN
                                                               Time base        1.0
                                                               Preset             1
                                                               Accumulated       0

                                              FS
                                                               CTU
                                                               COUNT-UP COUNTER       CU
                            OFF    ON                          Counter         C5:1
                                                               Preset             1   DN
                                                               Accumulated       0
                                   SS
                                              C5:1     T4:5                        Light

                                                    DN           DN
                                              C5:1     FS


                                                    DN
                                              SS
                                                                                   C5:1
                                                                                   RES


                          Figure 8-21  Alarm monitor program.



                 •  When the timer is running, SW (I:1/1) closed, the   8.3  Down-Counter
                    accumulated value changes rapidly.
                 •  Closing the momentary pushbutton PB (I:1/0)      The down-counter instruction will count down or dec-
                                                                     rement by 1 each time the counted event occurs. Each
                    will freeze and display the value at that point in   time the down-count event occurs, the accumulated
                    time.
                                                                     value is decremented. Normally the down-counter is
                  The alarm monitor PLC program of Figure 8-21 illus-  used in conjunction with the up-counter to form an up/
               trates the application of an up-counter used in conjunction   down-counter.
               with the programmed timed oscillator circuit studied in   Figure  8-22 shows the program and timing dia-
               Chapter 7. The operation of the program can be summa-  gram for a generic, block-formatted up/down-counter.
               rized as follows:                                     The operation of the program can be summarized as
                 •  The alarm is triggered by the closing of float switch FS.  follows:
                 •  The light will flash whenever the alarm condition is   •  Separate count-up and count-down inputs are
                    triggered and has not been acknowledged, even if      provided.
                    the alarm condition clears in the meantime.        •  Assuming the preset value of the counter is 3 and
                 •  The alarm is acknowledged by closing selector         the accumulated count is 0, pulsing the count-up
                    switch SS.                                            input (PB1) three times will switch the output light
                 •  The light will operate in the steady on mode when     from off to on.
                    the alarm trigger condition still exists but has been   •  This particular PLC counter keeps track of the
                    acknowledged.                                         number of counts received above the preset value.