Page 5 - 405E-FIRE-INRACK-01
P. 5

Technical Specification – Conventional Photoelectric Smoke Detector

Disposable Chamber Yes

Operating Voltage 9.5 - 30Vd.c.

Quiescent Current (typ) 35μA

Maximum Current Alarm 40mA

Remote Indicator Drive 20mA (max) / 9.5-14mA (typ)

Operating Temperature Range -10°C to + 50°C

Storage Temperature Range -30°C to + 60°C

Maximum Humidity 95%RH - Non Condensing (at 40°C)

Ingress Protection Rating IP42

Colour / Case Material Ivory White / ABS

Weight (g)     95

Diameter (mm)  100

Height (mm)    38

Base Heights (mm) 8 13

Base Fixing Centres (mm) 48 ~ 74

Approvals      EN54:2000 Part 7 LPCB VdS (G204043)

When the INSIDE is important, make the OUTSIDE Cannon.

                                                Cannon Technologies Ltd. www.cannontech.co.uk
                                               Queensway, New Milton, Hampshire, BH25 5NU. UK

                                                 Tel: +44 (0)1425 638148 Fax: +44 (0)1425 619276
                                                  Reg Office as above. Company Reg No. 1374913