Page 6 - drytec_process-air-drying
P. 6

Sorption drying provides ideal conditions












           Dew points below 5 °C cannot be effectively achieved
           with simple drying methods, such as condensation     Sorbent requirements (coating)
           drying – sorption drying is the only alternative.
                                                                »  High storage density

           The most important component of such a system is the   »  High adsorption effect at low water content
           sorption rotor with a special coating. It rotates at a speed
                                                                »  Desorption of the bound water with the lowest
           adapted to the process and absorbs the moisture from
                                                                  possible energy consumption
           the process air flow. In countercurrent, warm air is led
           through the sorption rotor, which removes the moisture
           from it. The water-laden exhaust air is then released to
           the environment outside the process area.




           How sorption drying works – operating principle of ULT Dry-Tec®





               1
                                          Moist air        Warm dry                 Cleaned dry


                             2                             regeneration air   7     ambient air



                                                            9        8
                                        3
                                                                              J
           process air
           Pre-cleaned moist
                                                             4                         Humid exhaust air


                             Preconditioned
                             process air

                                              Dry
           1  Process air pre-filter          process air               5                      6
           2  Pre-cooler
           3  Sorption rotor with drives                   process air
                                                           Conditioned, dry
           4  Post-cooler
           5  Process air ventilator
           6  Process air post filter
           7  Regeneration air filter                                        dry process air
           8  Heat exchanger
                                                                             Cleaned, conditioned,
           9  Electric heating
           J  Regeneration air fan



                        6
   1   2   3   4   5   6   7   8   9   10   11