Page 183 - FanPedia - By Aerovent
P. 183

®
 FAN-PEDIA                                                     SPECIAL CONSTRUCTION
 Published by   AEROVENT.COM
 Aerovent                                                                                            HIGH TEMPERATURE
 ©2017
 AXIAL FANS


                                                                GENERAL INFORMATION
 Arr. 4
 Aerovent packages:                                             Industrial processes often require high heat fans
 •  106 F to 140 F                                              that can withstand high temperature airstreams.
 o
 o
 •  141 F to 275 F
 o
 o
     (Requires Eng Review)                                      High Temp Materials
                                                                •  Standard Aluminum (Prop) – Up to 275 F
                                                                                                                                         o
                                                                •  A240 Aluminum – 276 F to 600 F
                                                                                                           o
                                                                                                                           o
                                                                •  Mild Steel & Stainless Steel
                                                                Bearing Requirements
                                                                •  Use High Temp Grease
                                                                •  Use Fixed & Floating Bearings
                                                                               > Refer to bearing basics section
                                                                •  Metal lube lines
                                                                Other Requirements
                                                                • Prop on outlet end of housing (outer shell)
                                                                                > Some models require Vane Section
                                                                • Fixed Prop required over 250 F
                                                                                                                       o
 Arr. 9  Retaining Washer Detail  Vane Section                   NOTE: Arr. 9 – Cool air is pulled into the bearing

                                                                housing through the belt tube


 Aerovent packages:
 •  141 F to 275 F
 o
 o
 •  276 F to 600 F
 o
 o








 (Select Fan Models)
              Retaining Washer                Safety Wire                Hardware                  Shaft Cooler                   Heat Shield                  Belt Tube