Page 586 - Basic Electrical Engineering
P. 586

4 W  + W  = 8.2 kW = 8200 W         (ii)
                                           c
                                                  cu
               From (i) and (ii),


                                                      W  = 1923 W
                                                         c


               and

                                                      W  = 507 W
                                                         cu


               Example 6.14   The equivalent circuit parameters of a 300 kVA, 2200/200 V,
               50 Hz single-phase transformer are: primary winding resistance, R  = 0.1 Ω;
                                                                                               1
               secondary winding resistance, R  = 0.01 Ω; primary leakage reactance, X  =
                                                                                                       1
                                                      2
               0.4 Ω; secondary leakage reactance, X  = 0.03 Ω; resistance representing core
                                                              2
                                                                                   3
                                   3
               loss, R  = 6 × 10  Ω, magnetizing reactance X  = 2 × 10  Ω. Calculate the
                                                                       m
                        c
               voltage regulation and efficiency of the transformer at full load at 0.8 power
               factor lagging.


               Solution:




















                                                          Figure 6.27

               We will consider E  = 2200 V and E  = 220 V
                                      1
                                                           2

               Transformation ratio,