Page 68 - Multi Mfg Catalog 09-12-2020
P. 68
MSH 2 ton - 4 ton Hyper Heat Heat Pump Outdoor Unit
Electrical Data
Model MSH-24HD-A MSH-36HD-A MSH-48HD-A
Power Supply V/Hz/Ph 208/230/60/1
Compressor Type Inverter
Packaging H x W x D 43 x 20 x 35 43 x 20 x 35 43 x 20 x 58.5
Packaged Weight Lbs 141 155 219
Noise Level dB(A) 59 64 64
Liquid - Suction Inch 3/8 - 5/8 3/8 - 5/8 3/8 - 5/8
Max Lineset
Length Feet 164 213 213
Max Lineset
Vertical Lift Feet 82 98 98
Refrigerant R410a R410a R410a
Refrigerant Feet 25 25 25
Precharge
Additional Charge Oz 0.32 0.32 0.32
Per Foot
Design Pressure Psi 550 550 550
Cooling Indoor 62°F / 90°F 62°F / 90°F 62°F / 90°F
DB Min / Max
Operating Range
Heating Indoor 32°F / 86°F 32°F / 86°F 32°F / 86°F
DB Min / Max
Ambient Range Outdoor -20°F / 118.4°F -20°F / 118.4°F -20°F / 118.4°F
Min - Max
Oper Volts Compressor Fan
Unit V / PH Max Min Input (W) Input (W) MCA Max Fuse
MSH-24HDA 253 187 1970 150 18 25
MSH-36HDA 208/230/1 253 187 2600 150 30 45
MSH-48HDA 253 187 3420 126 36.5 50
MCA - Minimum Circuit Ampacity
Multi Manufacturing LLC 2480 Grand Ave., Vista, CA 92081 Phone 760-670-3005 Fax 760-760-670-3307 www.multimfg-usa.com
7