Page 29 - RITAR INTELIGENTE MIL
P. 29
RA12-33 12V33Ah
Storage characteristic
15 100
Supplementary charge required
0℃ (Carry out supplementary charge
before use if 100% capacity is
(%) 80 10℃ Supplementary charge required
12 requires)
Expectancy (years) 9 6 Capacity 60 40℃ 30℃ 20℃ before use.
This supplementary charge will help
to recover the capacity and should
be made as early as possible.
40
fail to recover the capacity.
Life 20 Supplementary charge may often
The battery should never be left
standing till this state is reached
3
0
2 4 6 8 10 12 14 16 18 20 22 24 Supplementary charge and storage
0 guidelines
0 10 20 30 40 50 Storage Time (months)
Battery Temperature (℃)
Charge characteristic Curve for standby useharge characteristic Curve for standby use Discharge characteristic Curveischarge characteristic Curve
C
D
15 7.5 5.0 120 0.24
Chcrge Volume 13 6.5 4.3
14 7.0 4.7 100 0.20
Chcrge Voltage
(V) 12 6.0 4.0
Charge Voltage(V) 12 6.0 4.0 ① Discharge 60 Charge Volume 0.12 Charge Current (CA) Terminal Voltage 11 5.5 3.7 0.35C 0.16C 0.093C 0.05C
(%)
0.16
4.3
6.5
80
13
100%(0.05CA×20h)
50%(0.05CA×10h)
② Charge
Chcrge Voltage2.275V/C
5.0
3.3
10
Charge Current0.1CA
0.08
40
5.5
3.7
11
③ Temperature 25℃
3C 1C 0.62C
10 5.0 3.3 20 0.04 9 4.5 3.0
Charge Current
0.6 1.2 3 6 12 30 1 2 5 10 20 24
9 4.5 3.0 0 0
0 2 4 6 8 10 12 14 16 18 20 24 28 min Hr
Charge Time(h) Discharge Time
Capacity Factors With Different Temperature
Battery Type -20℃ -10℃ 0℃ 5℃ 10℃ 20℃ 25℃ 30℃ 40℃ 45℃
GEL 6V&12V 50% 70% 83% 85% 90% 98% 100% 102% 104% 105%
Battery 2V 60% 75% 85% 88% 92% 99% 100% 103% 105% 106%
AGM 6V&12V 46% 66% 76% 83% 90% 98% 100% 103% 107% 109%
Battery 2V 55% 70% 80% 85% 92% 99% 100% 104% 108% 110%
Discharge Current VS. Discharge Voltage Maintenance & Cautions
Float Service:
Final Discharge 1.75V 1.70V 1.60V
Voltage V/cell
※ Every month, recommend inspection every battery voltage.
Discharge (A)≥1.0C
Current (A) (A)≤0.2C 0.2C<(A)<1.0C
※ Every three months, recommend equalization charge for one time.
Equalization charge method:
Charge the batteries at least once every six months,
o
if they are stored at 25 C. Discharge: 100% rate capacity discharge.
Charging Method: Charge: Max. current 0.3CA, constant voltage 2.4-2.45V/Cell charge 24h.
※ Effect of temperature on float charge voltage: -3mV/℃/Cell.
Constant Voltage -0.2Cx2h+2.4-2.45V/cellx24h,Max. Current 0.3CA
※ Length of service life will be directly affected by the number of discharge
Constant Current -0.2Cx2h+0.1CAx12h
.
cycles, depth of discharge, ambient temperature and charging voltage.
Fast -0.2Cx2h+0.3CAx4.0h