Page 169 - PBL614 IM/SM500F-EN SM500F ( WIRO)
P. 169
SM500F
Field mountable paperless recorder
E.2 Relative Humidity Calculation
Relative humidity is calculated using the following formula:
VPSw – AP Td – Tw RH = 100 ------------
Appendix E – Math Equations
Where:
VPSw =
VPSd = Td = Tc = P = A = RH =
VPSd
Saturation Vapor Pressure at Wet Bulb Temperature Saturation Vapor Pressure at Dry Bulb Temperature Dry Bulb Temperature
Wet Bulb Temperature
Total Atmospheric Pressure (1000 mbar) Psychometric Constant (6.66 x 10–4)
% of Relative Humidity
A relative humidity calculation requires two inputs, one from a wet bulb sensor and one from a dry bulb sensor. Both of these inputs are incorporated into the equation as analog.
RH tables are based on the use of an aspirated psychrometer having an air velocity of at least 11.5 feet per second or 3.5 meters per second across the bulb sensors.
Inputs used for wet and dry bulb measurement must be in the ranges 0 to 100°C or 32 to 212°F. The result must be set to 0 to 100.0% RH.
Fig. E.1 (page 168) is an example of configuring a math block to perform a relative humidity calculation.
IM/SM500F Rev. AA 167