Field mountable paperless recorder 7 Configuration
7.3 Configuration Level Access
To configure the recorder when 'Configuration security' is set to the factory default setting of 'Password protected':
1. Access the Configuration Level – see Figs. 7.1 and 7.2, pages 66 and 67 respectively.
2. Make changes to parameters as detailed in Figs 7.5 and 7.6 (pages 70 and 71 respectively) and on-line help.
To configure the recorder when 'Configuration security' is set to 'Internal switch protected':
1. Set the internal security switch to the 'Configuration Level Not Protected' position – see Fig. 7.3, page 68.
2. Access the Configuration Level – see Figs. 7.1 and 7.2, pages 66 and 67 respectively.
3. Make changes to parameters as detailed in Figs 7.5 and 7.6 (pages 70 and 71 respectively) and on-line help.
Fig. 7.1 Accessing the Configuration Level
Displayed only if 'Security system' is set to 'Basic' – see Section 7.6.4, page 78
Configuration Level Protected
(see Section 7.2, page 65)
Configuration Level Unprotected (see Section 7.2, page 65)
Continued in Fig. 7.2 on next page
Displayed only if 'Security system' is set to 'Advanced' – see Section 7.6.4, page 78
Invalid Password Entered
Valid Password Entered