Field mountable paperless recorder 7 Configuration Referring to Fig. 7.3, set the internal security switch as follows:
a Unlock the recorder's door with the key supplied, press the release catch and open the door. Warning. Before proceeding to step 2, isolate the recorder from the power supply.
b Remove the tamper-evident seal (if fitted), release the captive screw securing the inner cover plate and remove the inner cover plate.
c Set the Security switch to the 'Configuration Level Not Protected' position (toward bottom of recorder).
d Locate the inner cover plate lugs in the slots in the outer case and close the inner cover plate.
e Tighten the inner cover plate retaining screw and fit a tamper-evident seal (if required).
f Close and lock the recorder's door and restore the power supply to the recorder.
Note. The Internal Security Switch is used to access the Configuration level when 'Configuration security' is set to 'Switch protected'. Do Not use the switch to access the Configuration level when 'Configuration security' is set to 'Password protected' (default setting) unless the Password has been forgotten. The switch overrides Password protection, enabling free access to the Configuration level.
Configuration Level Protected
Configuration Level Not Protected
Fig. 7.3 Setting the Security Switch
68 IM/SM500F Rev. AA