Page 76 - PBL614 IM/SM500F-EN SM500F ( WIRO)
P. 76

SM500F
Field mountable paperless recorder
7.6 Common Configuration
Fig. 7.8 Selecting Common Configuration
7 Configuration
           7.6.1 Setup
   Highlight the groups required.
button and press
to toggle the number of process
       •1
74
Each process group can have up to 6 recording channels assigned to it – Group 1 (Ch1.1 to 1.6), Group 2 (Ch2.1 to 2.6).
If the Number of Groups is changed from 2 to 1, configuration data for Process Group 2 is retained but not used.
Select the language to be used to display standard user prompts and menu items.
Note. A new language selection does not take effect until the configuration is saved.
Select a signal source used to acknowledge all active alarms in both Process Groups simultaneously. refer to Appendix A, page 146 for a description of the available sources.
Note. This signal is edge-triggered. A rising edge (inactive to active) or falling edge (active to inactive) triggers global alarm acknowledgement.
􏰺􏰤 Enter the tag to be used to identify the recorder on configuration and audit log files.
Note. When reviewing data, the instrument tag is used to identify the source of the data, therefore it is important to ensure that the instrument tag is unique to each recorder.
If this parameter is changed, internally recorded data files are recreated and unarchived data is lost. IM/SM500F Rev. AA
 