Page 95 - PBL614 IM/SM500F-EN SM500F ( WIRO)
P. 95
SM500F
Field mountable paperless recorder 7 Configuration
7.8 Channel Configuration
Process Group 1, Channels 1.1.to 1.6
Fig. 7.10 Recording Channel Configuration
7.8.1 Recording Channel Setup
Select the signal source for the selected channel. This can be any external analog or digital signal – see Appendix A, page 146 for full list.
Note.
The input source for Channel 1 in any process group must be an
analog source to ensure correct operation of the recorder.
The tabs change according to the selection made.
Setting a channel source to 'None' does not switch off the analog input to which the channel was assigned previously i.e. the analog input continues to be monitored. To switch off an analog input, set Analog I/P 'Type' for the required channel to 'Off' – see Section 7.8.2, page 96.
•1 If this parameter is changed from any previous setting other than 'None', a new internal data file for this recording channel is created. All historical data stored internally for this channel is lost. If this parameter is changed from a previous setting of 'None' new internal data files for all enabled recording channels are created. Any unarchived data is lost.
IM/SM500F Rev. AA 93