Page 260 - Civil Engineering Project Management, Fourth Edition
P. 260

Civil Engineering Project Management
                          240
                            Reliable values of S cannot be obtained unless enough sample results are
                          available. BS 5328 requires a minimum of 30 tests to be made before assessing
                          S; and for n   30 to 100 tests, the value S  should be taken where S   (0.86

                                                                    2
                            2/n )S, with a minimum value of 6N/mm . The DoE manual,  Design of
                          normal concrete mixes (1988), recommends that for Grades C20 and above, S
                                                                2
                          should be taken as not less than 8N/mm until more than 20 test results are
                                                                    2
                          available, and a minimum value of 4N/mm should apply however many
                          tests are taken. For trial mixes, values of 2S would also normally be taken
                          (rather than 1.64S) to give a further margin of safety. However, a less exacting
                          approach is also allowable as described in the next section.
                          19.3 Practical compliance with concrete standards
                          It can be seen that although designing a trial mix to meet a given grade can be
                          done within a reasonable time using recommended minimum S values, the
                          proving of a mix by statistical analysis of cube strengths is a lengthy business.
                          At least 20 batches of concrete would have to be made up (preferably 30 or
                          more) and at least two cubes from each batch tested at 28 days. (BS 5328
                          requires the mean of two cubes to be taken in each case.) The statistical method
                          is therefore mainly used to monitor concrete quality when large quantities
                          are being placed, and is not practicable for small sites. However, BS 5328 laid
                          down simpler criteria for concrete of grades C20 and above, namely:
                          • the average cube strength of four consecutive samples must exceed the
                                                                    2
                             desired characteristic strength by 3N/mm ;
                                                                      2
                          • no single test shall be more than 3N/mm less than the characteristic
                             strength.
                            Thus four batches tested are the minimum requirement for testing of a trial
                          mix. As an example, a trial mix for Grade C25 characteristic strength would be
                          satisfactory if samples from each of four batch mixes give an average strength
                                                                                            2
                                                 2
                          of not less than 28N/mm with no single cube strength under 22N/mm .
                            The specification may also set other requirements such as minimum cement
                          content, minimum density of concrete, and minimum tensile strength under
                          bending. BS 1881 (1981): Methods of testing concrete describes (inter alia) standard
                          methods of sampling mixes, making and curing test specimens, density testing,
                          and tensile testing – the latter labelled ‘determination of flexural strength’.
                          Cubes are usually tested in an off-site laboratory. A density test can be carried
                          out on site provided it is defined as on ‘fresh, fully compacted concrete’ (see
                          Section 19.8). The requirement for the flexural test is shown in Fig. 19.1. A test
                          apparatus is simple to make on site, and the tensile strength of the concrete is
                          easily calculated from the value of the central load which causes failure of the
                          beam. This tensile strength is important in water retaining concrete, and can be
                          helpful in deciding when support props can be removed from slabs and beams
                          if the test beam is cured alongside and in the same manner as such slabs and
   255   256   257   258   259   260   261   262   263   264   265