Chapter 1
Figure 4 Clearances for transformers from structures
COMBUSTIBLE BUILDING WALLS AND ROOF 10' COMBUSTIBLE BUILDING WALLS AND ROOF
10' 3'
10'
APPROVED APPROVED
TRANSFORMER TRANSFORMER
AREA AREA
10' 3'
TRANSFORMER CLEARANCES FROM COMBUSTIBLE SURFACES REDUCED FLAMMABILITY TRANSFORMER CLEARANCES
FROM COMBUSTIBLE SURFACES
NONCOMBUSTIBLE COMBUSTIBLE
ROOF AND ROOF AND
SOFFIT SOFFIT
3' 10'
NONCOMBUSTIBLE BUILDING WALLS 10' NONCOMBUSTIBLE BUILDING WALLS
3'
APPROVED
TRANSFORMER
AREA APPROVED
TRANSFORMER
3' AREA 3'
TRANSFORMER CLEARANCES FROM TRANSFORMER CLEARANCES FROM
NONCOMBUSTIBLE SURFACES NONCOMBUSTIBLE WALLS WITH COMBUSTIBLE ROOFING
Electric Service Handbook 2017 — Single-Family Residential Projects 13