Page 7 - S Type EBook Data Sheet Rev 0
P. 7
J3C-S20-85 Smart Electric Valve Actuator
25-90Nm Range in Models: S20, S35, S55, S85
Available with actuator function: POWER OPEN - POWER CLOSE FAILSAFE MODULATING FAILSAFE MODULATING
J3C-S ELECTRIC ACTUATOR MULTI-COLOUR LED STATUS LIGHT
Actuator operational status LED Colour
No power being supplied Off
Power being supplied to actuator If OPEN = Green, if CLOSED = RED
Actuator moving between open and closed Open to close = flash Orange / Red, Close to open = flash Orange / Green
Actuator in MANUAL mode Flash Orange / Off (symmetrical sequence)
Torque limiter activated If closing when activated = flash Red / Off, if opening = flash Green / Off
BSR failsafe system activated If configured Fail Close = flash Red / Off, if Fail Open = Green / Off (Max 3 mins)
BSR Battery needs charging warning Flash Orange / Off (asymmetrical sequence)
Actuator with DPS(2015) positioner Opening = flash Blue / Green, Closing = Blue / Red, Stationary = Blue
J3C-S ELECTRIC ACTUATOR BSR FAILSAFE SYSTEM SPECIFICATIONS
Detail J3C-S-20 J3C-S-35 J3C-S-55 J3C-S-85
Initial charge time BEFORE being placed into operational service 28 Hours 28 Hours 28 Hours 28 Hours
Maximum movements with fully charged battery 5 5 5 5
Minimum recharge time after each movement 8 mins 8 mins 10 mins 20 mins
Battery consumption when power drawn from battery 6.2W 6.2W 6.2W 6.2W
Nominal battery capacity 1000mA 1000mA 1000mA 1000mA
Current drawn when operating by battery 2.4mA 2.4mA 3.3mA 7.1mA
Charge consumption 36mA/h 36mA/h 36mA/h 36mA/h
System to change between fail close & fail open PCB jumper PCB jumper PCB jumper PCB jumper
J3C-S ELECTRIC ACTUATOR DPS MODULATING SYSTEM SPECIFICATIONS
Detail J3C-S Series
Input/ Output options 0-10V, 1-10V, 0-20mA, 4-20mA
Output shaft feedback system Magnetic, digital
Accuracy, linearity, hysteresis, repeatability Better than 2%
In the interest of product improvement, specifications may change without Doc: J3C-S-EBook Rev.0 May 17