Page 204 - Gas Detection Systems Training Manual
P. 204

Once it is complete and successful, the popup status is removed and the “Change Alarm Levels” screen returns to its original appearance when it was first displayed, only containing the new alarm threshold level values.
6.2.2 Changing the Alarm Active Mode Settings
Pressing the “Change Alarm Active Mode Settings” button from the Navigation panel on any of the Sensor configuration screens, as shown below:
Will display the “Alarm Active Modes” Screen:
By choosing one of the above alarm threshold active mode text fields/current values (low, mid or high), you can choose to either have the given alarm trigger when the gas value rises above the threshold set point, or trigger when the gas value falls below it.
Sensor Electronics Corporation 5500 Lincoln Drive Minneapolis, Minnesota 55436 September 29th, 2006
Page 20 of 66
952-938-9486
SEC 3500 OI Supervisor Operator’s Manual Version 2.1.0095