If so, then this is either the first time the 3500 has been powered on, or you do not have the Gas Monitoring loop setup/configured properly, or you have not detected any SEC 3500 compatible devices yet. Otherwise, if at least one compatible device is connected, online and had been setup previously, then at least one of the sixteen zone summary boxes would be green- see below:
(Menu Button Areas)
If this is the first time startup, or scanning the loop for new devices, refer to the
“Startup Basics Guide” and “Supervisor’s Manual” to establish the panel.
4.0 Basic Screen Navigation
The goal of this section is to describe the basic screens and their touch-screen navigation methods that provide the normal operational information at all the different information levels:
• Level 1- Device. Information is captured at the lowest level; every SEC 3100 Digital
Gas Transmitter device connected to the SEC 3500 Primary Modbus Gas Transmitter Loop. Under normal operation, only Gas level and Transmitter status is captured for each SEC 3100 device on the loop, once per scan, repeated infinitely.
• Level 2- Zone. Per scan, Gas levels and alarm states are collected, sorted and summarized into the sixteen different zones shone on the “Main Zone Summary” screen. Each device can only be assigned to one of these sixteen zones. The highest alarm level (highest possible level is a Fault) of all devices in each zone determine each zone alarm rollup level.