Page 2 - Pocket Guides
P. 2

POCKET GUIDE                                 1-2


   GUIDE TO SITING EQUIPMENT IN A LOCATION
   CONTAINING A BATH OR SHOWER
   The general requirements in Parts 1 to 6 of the Regulations are applicable within the
   zones of a location containing a bath or shower but are supplemented by the additional
   requirements in Part 701 of BS 7671.



                                  Zone 1
                   *       Zone 1

                                              Zone 2
                                        Zone 2
                Outside
                zones                             2.25 m
         Outside                  Zone 0
         zones                              2.25 m
                           Zone 0
                 The space underneath the bath is   0.6 m
                zone 1 if accessible without the use
          The space underneath the bath is   0.6 m
                 of a tool, or outside the zones if
          zone 1 if accessible without the use
               accessible only with the use of a tool
           of a tool, or outside the zones if
         accessible only with the use of a tool  * A window recess is zone 2




                            Zone 1
                2.25 m               Zone 2
                     Zone 1
          2.25 m               Zone 2      Outside
                                           zones
                                     Outside
                                     zones
                            Zone 0
                     Zone 0
                        0.6 m
                              For showers without a basin there is no
                  0.6 m       zone 2, but the horizontal dimension of
                       For showers without a basin there is no
                              zone 1 is increased to 1.20 m (701.32.3 (ii) (b))
                       zone 2, but the horizontal dimension of
                       zone 1 is increased to 1.20 m (701.32.3 (ii) (b))
     Notes:
     - All low voltage circuits either serving the location or passing through zones 1
      and/or 2 but not serving the location must have additional protection provided
      by  one  or  more  RCDs  that  have  a  rated  residual  operating  current (I   )  not
                                                ∆n
      exceeding 30 mA (701.411.3.3).
     - Providing all final circuits of the location have additional protection, meet the
      requirements for automatic disconnection and the installation is fitted with
      effective protective equipotential bonding, then supplementary equipotential
      bonding may be omitted (701.415.2).