Page 34 - Pocket Guides
P. 34

POCKET GUIDE                                  19


    SIZING EARTHING CONDUCTORS
   This Guide gives information on determining the cross-sectional area (csa) for an
   earthing conductor as required by BS 7671.

      THE EARTHING CONDUCTOR OF AN INSTALLATION IN RELATION
      TO THE MET AND THE MEANS OF EARTHING

                              Circuit protective conductors
                              and main protective
                              bonding conductors


                              Main Earthing Terminal


                              Earthing conductor

            Distributor’s earthing
            facility (TN system)
            or installation   Means of earthing
            earth electrode
            (TT or IT system)



    Regulation  542.3.1  requires  that  every
    earthing conductor must comply with   POCKET GUIDE
                                                 13
    Section 543, which includes determining   SIZING MAIN PROTECTIVE BONDING CONDUCTORS

    the csa required by selection or   This Guide gives information on the sizing of main protective bonding conductors,
                                 based on the requirements given in Regulation Group 544.1 of BS 7671.
    calculation (see Pocket Guides 14 or 15,   protection for protection against electric shock where the protective measure is  14
                                   POCKET GUIDE
                                 Protective equipotential bonding is a provision under the requirements for fault
                                Automatic Disconnection of Supply (ADS).
    respectively).              Where the protective measure is ADS, in each installation main protective bonding

                                ARRANGEMENT OF PROTECTIVE EQUIPOTENTIAL BONDING
                                   SIZING OF PROTECTIVE CONDUCTORS BY SELECTION
                                   Regulation Group 543.1 of BS 7671 requires that a protective conductor other than
    Where PME conditions apply, the csa of   the main earthing  terminal the extraneous-conductive-parts of that installation
                                conductors complying with Chapter 54 of  BS7671 are required to connect to
                                  protective bonding conductor is sized either by calculation or selection.This guide
                                  covers the sizing of protective conductors by selection, using Table 54.7.
                                 •  water installation pipes
                                    POCKET GUIDE
    an earthing conductor must also meet   •  other installation pipework and ducting
                                including: It should be noted that where the choice of the cross-sectional-area (csa) of the line
                                 •  gas installation pipes
                                  conductors has been determined by considerations of short-circuit current, and if  15
                                  of the protective conductor must be calculated (543.1.1).
                                  the earth fault current is expected to be less than the short-circuit current, the csa
                                  MINIMUM PROTECTIVE CONDUCTOR SIZES
    the requirements of Regulation 544.1.1   •  exposed metallic structural parts of the building.
                                    SIZING OF PROTECTIVE CONDUCTORS BY CALCULATION
                                •  central heating and air conditioning systems
                                    Regulation Group 543.1 of BS 7671 requires that a protective conductor other
                                    than  an  protective  bonding  conductor  is  sized  either  by  calculation  or
    of a main protective bonding conductor  with BS EN 62305 (411.3.1.2).
                                  Certain lower limits apply to the csa of a protective conductor. The size of the  selection.
                                 protective conductor used must be not less than the appropriate limiting value (see
                                 below) and not less than that determined by selection (see later).
                                   This Guide covers the sizing of protective conductors by calculation, which uses
                                   conductors by selection is given in Pocket Guide 14.
                                   the adiabatic equation, as explained later. Information on sizing of protective
                               Any bonding to a lightning protection system must be carried out in accordance
                                 Where a protective conductor is not an integral part of a cable (such as a ‘twin & earth’
    (see Pocket Guide 13).      Pocket Guide 13).
                                 cable or an armoured cable); or formed by conduit, ducting or trunking; or contained
                                 in an enclosure formed by a wiring system, the csa of the protective conductor must
                                  Extraneous-conductive-part
                                   A protective conductor must always be sized by calculation where the line conductor
                                 other than pipework
                                   has been sized by considerations of short-circuit current and if the earth fault current
                                   is expected to be less than the short-circuit current (543.1.1).
                                 not be less than 2.5 mm 2  copper equivalent if protection against mechanical damage
                                 (eg exposed structural metalwork)
                                   MINIMUM PROTECTIVE CONDUCTOR SIZES
                                 protection against mechanical damage is not provided (543.1.1).
                                 is provided (such as by a sheath), and not less than 4 mm 2  copper equivalent if
                                 Where PME conditions apply, a protective conductor used as an earthing conductor
                                   Certain lower limits apply to the cross-sectional-area (csa) of the protective
                                  discussed in Pocket Guide 14.
                                     Main protective
                                  conductor. The size of the protective conductor used must not be less than the
                                must have a csa not less than that required by Regulation 544.1.1 (refer to NICEIC
                                     bonding conductors
                                  limiting  values given in Regulations  543.1.1  and, where  applicable, 544.1.1  as
                                required by Table 54.1 of BS 7671.
                                          Water
                                            Gas
                                         meter
                                A protective conductor buried in the ground must have a csa not less than that
                                  CALCULATING THE SIZE OF THE PROTECTIVE CONDUCTOR
                                            meter
                                SELECTING THE SIZE OF THE PROTECTIVE CONDUCTOR
                                 Main Earthing Terminal
                                  The csa of the protective conductor, where calculated, is to be no less than the
                                  value (S) determined using the adiabatic equation (543.1.3).
                                        Metallic
                                       pipework
                                         S =    I 2 t
                                The process of selection uses the csa (S) of the associated line conductor and
                                 Where:          k
                                Table 54.7 of  BS 7671 (Data reproduced below in part). Where the protective
                               be used.
                                conductor is common to several circuits,  its csa should be based on the csa of the
                                 S
                             WHERE PROTECTIVE MULTIPLE EARTHING (PME) CONDITIONS DO NOT APPLY
                               largest line conductor of the circuits (543.1.2). Where selection produces a non-
                                 I    is the nominal csa of the protective conductor in mm 2 .
                               DATA FROM TABLE 54.7 OF BS 7671
                             Where PME conditions do not apply, Regulation 544.1.1 requires a main protective
                               standard size, a conductor having at least the nearest larger standard csa should
                             bonding conductor to have a cross-sectional area (csa) of not less than half the csa
                             required for the earthing conductor of the installation, and not less than 6 mm 2 .
                               conductor S (mm 2 )
                                      S  ≤ 16
                            affording equivalent conductance in other metals.
                            The csa need not exceed 25 mm 2  if the bonding conductor is of copper, or a csa
                                  is  the  value  in  amperes  (rms  for  AC)  of  the  fault  current  for  a  fault
                               Minimum csa of the
                                          16 < S ≤ 35
                            WHERE PME CONDITIONS APPLY
                               CSA of line  of negligible impedance, which can flow through the associated
                                     A        S > 35
                               corresponding
                                  protective device.
                                t      S
                                  protective device, due account being taken of the current limiting
                               protective conductor
                               (mm 2 )     16  S
                                  effect of the circuit impedances and the limiting capability (I 2 t) of that
                                    B         2
                                       S
                                          k 1
                                k    corresponding to the fault current (I) in amperes.   k 1
                                           X 16
                                          k 2 updated to  S
                                  is the operating time of the disconnecting device in seconds
                                              X 2
                                              k 2
                                            TH
                              Row B of the above table, as applicable.
                                          BS 7671:2018 updated to
                                            EDITION
                              The csa of the protective conductor must be not less than required by Row A or
                                  © CERTSURE LLP 2019
                                 is a factor taking account of the resistivity, temperature coefficient and
                                 final temperatures of the conductors.
                                 heat capacity of the conductor material, and the appropriate initial and
                              Row A should be used where the protective conductor
                              is of the same material as the associated line conductor.
                                nearest larger standard csa should be used.
                              Row B should be used where the protective conductor is
                                         updated to  TH
                                Where  a  non-standard  size  is  calculated,  a  conductor  having  at  least  the
                              not of the same material as the associated line conductor.
                                           TH updated to
                                           EDITION
                               Where the protective conductor is common to several circuits, the calculation
                               circuits (543.1.2).  EDITION
                                              TH
                               process should be based on the most onerous values of fault current (I) and
                                         BS 7671:2018
                                              EDITION
                               operating time (t) (or energy let-through (I 2 t)) encountered in each of the
                                    © CERTSURE LLP 2019
                                           BS 7671:2018
                                            BS 7671:2018
                      © CERTSURE LLP 2019
                                           updated to
                                             TH
                                             updated to
                                             EDITION
                                               TH
                                           BS 7671:2018
                                               EDITION
                                     © CERTSURE LLP 2019
                                            updated to
                                            BS 7671:2018
                                            updated to
                                                  TH
                                              TH
                                              EDITION
                                                  EDITION
                                            BS 7671:2018
                                            BS 7671:2018
   29   30   31   32   33   34   35   36   37   38   39