Page 10 - Pocket Guides
P. 10
POCKET GUIDE 6
Cables outside 150 mm 150 mm
the zone (see note 3)
Cables outside 150 mm 150 mm
PERMITTED CABLE ROUTE ZONES
the zone (see note 3)
150 mm
Cables outside
150 mm
Cooker the zone (see note 3) 150 mm 150 mm
control
switch Cooker
control
switch
150 mm
Light switch
Cooker reverse side
control Light switch
switch reverse side
Entrance
to room 2
13 A socket-outlet Entrance
Cooker this side 13 A socket-outlet Light switch to room 2
connection Cooker this side reverse side
point connection
point Entrance
to room 2
13 A socket-outlet
Cooker this side
connection
point
Fig 1. Zones in room 1
150 mm
150 mm
150 mm
150 mm 150 mm
Light switch Light switch
this side this side
150 mm
Entrance Entrance
from room 1 from room 1 Light switch
13 A socket-outlet 13 A socket-outlet
this side
reverse side reverse side
Entrance
100 mm or less 100 mm or less
from room 1
13 A socket-outlet
reverse side
Fig 2. Zones in room 2 100 mm or less
Zone within 150 mm from the top of the wall or partition
Zone within 150 mm from the top of the wall or partition
Zone within 150 mm of an angle formed by two adjoining walls or partitions
Zone within 150 mm of an angle formed by two adjoining walls or partitions
Horizontal and vertical zones for an accessory on this side of the wall or partition
Horizontal and vertical zones for an accessory on this side of the wall or partition
Zone within 150 mm from the top of the wall or partition
Horizontal and vertical zones for an accessory on the reverse side may extend to this side (see note 4).
Horizontal and vertical zones for an accessory on the reverse side may extend to this side (see note 4).
Zone within 150 mm of an angle formed by two adjoining walls or partitions
updated to
Horizontal and vertical zones for an accessory on this side of the wall or partition
TH
Horizontal and vertical zones for an accessory on the reverse side may extend to this side (see note 4).
EDITION
BS 7671:2018
© CERTSURE LLP 2018
updated to
TH
EDITION
BS 7671:2018