Page 13 - Gas insulated Switchgaer
P. 13

Circuit Breaker







                                    1. Circuit Breaker ตองมีขนาดพิกัดไมนอยกวาคา ดังตอไปนี้


                                           Rated voltage                                       : 24 kV



                                           Rated insulation level


                                           - Lightning impulse withstand voltage  : 125 kV peak


                                           - One minute power frequency



                                           Withstand voltage                                   : 50 kV RMS


                                     Rated frequency                            : 50 Hz


                                     Rated normal current                       : 1,250 A



                                     Rate breaking capacity                     : 25 kA RMS, 3 sec


                                     Rate operating sequence                    :O-0.3Sec-CO-15Sec-O


                                     Electrical endurance                       : ไมนอยกวา E2



                                      Mechanical endurance                      : ไมนอยกวา M2


        ตองแนบผลทดสอบเพื่อการพิจารณาดวย


               2. Circuit Breaker ตองสามารถใชมอเตอรไฟฟาเปนตัวชารจสปริง แหลงจายสําหรับการ


        ทํางานของอุปกรณและวงจรควบคุมการทั้งหมดใหใชแรงดัน 110-230 VAC/VDC


               3. Circuit Breaker ในตู Switchgear แรงสูงที่ใชตองเปนชนิด Vacuum แบบ Fixed

        Type, totallyclosed and maintenance free contact ผลิตและทดสอบตาม IEC 62271-


        200


               4. เมื่อ Power supply ขาดหายไป, spring ของ operating mechanism ตองมีกําลัง


        เพียงพอสําหรับสั่ง Circuit Breaker ให OFF-ON-OFF ได 1 sequence
   8   9   10   11   12   13   14   15   16