Page 7 - Gas insulated Switchgaer
P. 7

Interlocks








               กลไกอินเตอรล็อคของ three-position switch และ circuit-breaker ภายในตู

       สวิตชเกียรฯ ตองมีคุณสมบัติ ดังนี้:



               1. Operation of three-position switch cannot be selected as long as the



       circuit-breaker is closed. The selection “operate three-position switch” locks


       out the circuit-breaker.


               2 .Selecting “disconnector function” or “earthing switch function” only



       releases the  operating shaft for the associated switching operation. The


       operating lever can not be removed until the switching operation has been


       completed.



               3 .“Operate three-position switch” can not be completed until the


       operating lever has been removed.



               4. Feeder earthing (three-position switch to EARTH and circuit-breaker


       ON) is secured against de-earthing. Electrical connections to the releases are


       interrupted by auxiliary contacts of the



        three-position switch in EARTHED position.



       Local mechanical opening of the circuit-breaker



        can be blocked. This is made by blocking the



       tripping latch, which also prevents the



       circuit-breaker from being tripped by other external effects.