Page 151 - Select Specialty
P. 151
Oil-Less Claw Medical Vacuum
Appendix B: Variable Speed Drive Inverter
B.2.2 Parameter List (continued)
Minimum
Setting Initial Factory
Function Parameters Name Setting Range Increments Value Setting
261 Power failure stop selection 0, 1, 2 1 0 2 +
Subtracted frequency at
262 deceleration start 0 to 20Hz 0.01Hz 3Hz
Power failure stop 263 Subtraction starting frequency 0 to 120Hz, 9999 0.1/0.01s 60Hz
0.01Hz
Power-failure deceleration time
264
5s
0 to 3600/ 360s
1
Power-failure deceleration time
265
9999
2 0 to 3600/ 360s, 0.1/0.01s 9999
Power failure deceleration time
266 0 to 400Hz 0.01Hz 60Hz
switchover frequency
---- 267 Terminal 4 input selection 0, 1, 2 1 0 1 +
---- 268 Monitor decimal digits selection 0, 1, 9999 1 9999
---- 269 Parameter for manufacturer setting. Do not set.
Rotation direction detection
---- 299 0, 1, 9999 1 9999
selection at restarting
300 BCD input bias
301 BCD input gain
Digital input 302 BIN input bias Parameter for digital input option (FR-A7AX)
303
BIN input gain
compensation enable/disable
304 Digital input and analog input
selection
305 Read timing operation selection
306 Analog output signal selection
307 Setting for zero analog output
Setting for maximum analog
308 output
Analog output 309 Analog output signal voltage/ Extension analog output/digital output option
current switchover
Parameter for (FR-A7AY)
Analog meter voltage output
310
selection
Setting for zero analog meter
311
voltage output
Setting for maximum analog
312
meter voltage output
+ Indicates setting changed from initial value
4107 9000 95.04 B-12