ZONE VALVE/ AREA ALARM / OUTLET PERFORMANCE/GAS CONCENTRATION AND PURITY INSPECTION DOCUMENT
Facility Florida Hosp. Orlando – Women’s Center Inspector Joseph Voight
City/State Orlando, FL Date 11-28-17 Page 1 of 5
Contractor n/a Facility Contact Darrell Huckaby
th
Area Served Patient Rooms 10917-10928 Floor/Bldg 10 Floor
Zone Valve Location for this Area Corridor wall across from Rm 10919 ZVB Manufacturer Amico – 4 Valves
FL Hosp. Tag # O2 000000244444 AIR 000000244443 VAC 000000244442
Location IAW NFPA 99 Pass Labeled Pass Gauges Pass Leak Test Pass
Test Gauge O2 52 AIR 49 VAC 22
Pressure vs.
ZVB Gauge 54 50 22
Valve Size ¾” ¾” 1 ½”
Comments:
Gas/Pipeline Purity Oxygen Med Air Comments
Hydrocarbons <1 PPM <1 PPM
Dew Point -44F 5F
Carbon Monoxide <1 PPM <1 PPM
Carbon Dioxide 0 PPM 120 PPM
Gas Concentration 99%O2 21.8(%O2)
Particulates None None
Odor/Discoloration None None
Test Location 10926 10926
Area Alarm Panel Location for this Area Nurses station wall across from Rm 10922
Location IAW NFPA 99 Pass Labeled Pass Gauges Pass Leak Test Pass
Area Alarm Panel Manufacture Data Amico LCD ADV# 000000244425
GAUGE LOW HIGH TEST
GAS/VAC PSI ALARM ALARM VISUAL AUDIBLE SWITCH SENSOR COMMENTS PASS/FAIL
OXY 53 40 60 P P P PS PASS
AIR 49 40 60 P P P PS PASS
VAC 21 12 NA P P P PS PASS
PS= Patient Side SS= Source Side NW= Not Working CNT= Could Not Test NA = Not Applicable NP = Not Present