Page 152 - Womens Pavilion
P. 152

ZONE VALVE/ AREA ALARM / OUTLET PERFORMANCE/GAS CONCENTRATION AND PURITY INSPECTION DOCUMENT

           Facility    Florida Hosp. Orlando – Women’s Center  Inspector  Joseph Voight
           City/State   Orlando, FL                           Date       11-28-17        Page       1 of 7

           Contractor  n/a                                    Facility Contact   Darrell Huckaby
                                                                             th
          Area Served   Patient Rooms 12901-12916             Floor/Bldg   12  Floor

           Zone Valve Location for this Area   Corridor wall across from Rm 12913  ZVB Manufacturer   Amico

          FL Hosp. Tag #       O2 000000244432 AIR 000000244431 VAC 000000244430
          Location IAW NFPA 99   Pass          Labeled    Pass      Gauges   Pass       Leak Test   Pass
           Test Gauge   O2    52   AIR    49   VAC    21
           Pressure vs.
           ZVB Gauge          51          50          21

          Valve Size       ¾”          ¾”         1 ½”
          Comments:


         Gas/Pipeline Purity  Oxygen      Med Air       Comments
         Hydrocarbons             <1 PPM         <1 PPM
         Dew Point                   -44F            5F
         Carbon Monoxide          <1 PPM         <1 PPM
         Carbon Dioxide            0 PPM        120 PPM
         Gas Concentration        99%O2       21.8(%O2)
         Particulates               None           None

         Odor/Discoloration         None           None
         Test Location             12913          12913

         Area Alarm Panel Location for this Area         Nurses station wall across from Rm 12922

         Location IAW NFPA 99       Pass                 Labeled    Pass   Gauges     Pass     Leak Test   Pass
         Area Alarm Panel Manufacture Data         Amico LCD ADV# 000000244428
                     GAUGE     LOW      HIGH                        TEST
          GAS/VAC      PSI    ALARM    ALARM    VISUAL   AUDIBLE   SWITCH   SENSOR        COMMENTS        PASS/FAIL
            OXY        52       40       60       P        P         P         PS                           PASS
             AIR       49       40       60       P        P         P         PS                           PASS
            VAC        19       12       NA       P        P         P         PS                           PASS
           PS= Patient Side   SS= Source Side   NW= Not Working   CNT= Could Not Test   NA = Not Applicable    NP = Not Present





              Corporate Office ∙ 4518 Clements Rd. Lakeland Florida 33811 Phone: 863-646-7555 ∙ Fax 863-646-2999
                                 “Medical Gas Pipeline Equipment Service, Sales & Verifications”
                                                      ©Daniel Voight 2009
   147   148   149   150   151   152   153   154   155   156   157