ZONE VALVE/ AREA ALARM / OUTLET PERFORMANCE/GAS CONCENTRATION AND PURITY INSPECTION DOCUMENT

           Facility    Florida Hosp. Orlando – Women’s Center  Inspector  Anthony Voight
           City/State   Orlando, FL                           Date       11-29-17        Page       1 of 5

           Contractor  n/a                                    Facility Contact   Darrell Huckaby
                                                                           th
          Area Served   NICU 4913-4920, 4935-4938             Floor/Bldg   4  Floor

           Zone Valve Location for this Area   Across from Med Room A      ZVB Manufacturer     Beacon

          FL Hosp. Tag #       O2-000000311168   AIR-000000311169   VAC-000000311170
          Location IAW NFPA 99   Pass          Labeled    Pass      Gauges   Pass       Leak Test   Pass
           Test Gauge   O2    52   AIR    48   VAC    20
           Pressure vs.
           ZVB Gauge          53          49          22

          Valve Size       ¾”          ¾”         1 ¼”
          Comments:


         Gas/Pipeline Purity  Oxygen       Med Air      Comments
         Hydrocarbons              <1 PPM        <1 PPM
         Dew Point                    -44F           5F
         Carbon Monoxide           <1 PPM        <1 PPM
         Carbon Dioxide             0 PPM       120 PPM
         Gas Concentration         99%O2      21.8(%O2)
         Particulates                None          None

         Odor/Discoloration          None          None
         Test Location               4913          4913

         Area Alarm Panel Location for this Area         Across from Med Room A

         Location IAW NFPA 99       Pass                 Labeled    Pass   Gauges     Pass     Leak Test   Pass
         Area Alarm Panel Manufacture Data         Beacon Total Alert Infinity ADV# 000000311166
                     GAUGE     LOW      HIGH                        TEST
          GAS/VAC      PSI    ALARM    ALARM    VISUAL   AUDIBLE   SWITCH   SENSOR        COMMENTS        PASS/FAIL
            OXY        53       40       60       P        P         P         SS                           PASS
             AIR       48       40       60       P        P         P         SS                           PASS
            VAC        22       12       NA       P        P         P         SS                           PASS
           PS= Patient Side   SS= Source Side   NW= Not Working   CNT= Could Not Test   NA = Not Applicable    NP = Not Present





              Corporate Office ∙ 4518 Clements Rd. Lakeland Florida 33811 Phone: 863-646-7555 ∙ Fax 863-646-2999
                                 “Medical Gas Pipeline Equipment Service, Sales & Verifications”
                                                      ©Daniel Voight 2009