Page 443 - Womens Pavilion
P. 443
TotalAlert Infinity™ NFPA Medical Gas Notification System
1.2.2 Master Alarm 1.2.5 Boards
Features: NOTE:
Monitors up to 60 normally closed dry-con- I = 4-20mA Inputs
tact switch signals wired locally. X = Source Signal Inputs
Y = Dry-Contact Relay Outputs
• Consolidated view gives easy to read over- D = Digital Gas Sensor Inputs
view of all source equipment status
• Monitors additional source signals from B03 Advance Board
up to 8 remote alarm panels via wired
Ethernet connection Features:
1.2.3 Area Alarm Contains hardware for advanced features of
the TotalAlert Infinity™ Alarm.
Features:
Monitors up to 8 Digital gas sensors.
• Digital pressure/vacuum read out with
Low/Normal/High indicators
• Customizable gas ID labels with user-de-
fined location labels for each monitored
gas
• Rough-in box capable of holding 8 locally
mounted sensors
• Gas Specific DISS connections for each gas
sensor
• Gas Specific Digital ID for each gas sensor Figure 3: B03 Advanced Board
1.2.4 Combination Alarm
Monitors a mix of normally closed dry-con-
tact switch signals, digital gas sensor mod-
ules, and 4-20mA transducers.
Features:
• User-defined values for monitoring any 2
or 3 wire 4-20mA transducer
4107 9016 58.02 1-2