ZONE VALVE/ AREA ALARM / OUTLET PERFORMANCE/GAS CONCENTRATION AND PURITY INSPECTION DOCUMENT

           Facility    Florida Hosp. Orlando – Women’s Center  Inspector  Anthony Voight
           City/State   Orlando, FL                           Date       11-29-17        Page       1 of 2

           Contractor  n/a                                    Facility Contact   Darrell Huckaby
                                                                           th
          Area Served   RT Equipment Room 4168                Floor/Bldg   4  Floor

           Zone Valve Location for this Area   Outside RT Room             ZVB Manufacturer     Beacon

          FL Hosp. Tag #       O2-000000311172   AIR-000000311173
          Location IAW NFPA 99   Pass          Labeled    Pass      Gauges   Pass       Leak Test   Pass
           Test Gauge   O2    52   AIR    48
           Pressure vs.
           ZVB Gauge          52          50

          Valve Size       ¾”          ¾”
          Comments:


         Gas/Pipeline Purity  Oxygen       Med Air      Comments
         Hydrocarbons              <1 PPM        <1 PPM
         Dew Point                    -44F           5F
         Carbon Monoxide           <1 PPM        <1 PPM
         Carbon Dioxide             0 PPM       120 PPM
         Gas Concentration         99%O2      21.8(%O2)
         Particulates                None          None

         Odor/Discoloration          None          None
         Test Location                 RT            RT

         Area Alarm Panel Location for this Area         NO ALARM FOR THIS ZONE















              Corporate Office ∙ 4518 Clements Rd. Lakeland Florida 33811 Phone: 863-646-7555 ∙ Fax 863-646-2999
                                 “Medical Gas Pipeline Equipment Service, Sales & Verifications”