Page 62 - Womens Pavilion
P. 62
ZONE VALVE/ AREA ALARM / OUTLET PERFORMANCE/GAS CONCENTRATION AND PURITY INSPECTION DOCUMENT
Facility Florida Hosp. Orlando – Women’s Center Inspector Anthony Voight
City/State Orlando, FL Date 11-29-17 Page 1 of 2
Contractor n/a Facility Contact Darrell Huckaby
th
Area Served RT Equipment Room 4168 Floor/Bldg 4 Floor
Zone Valve Location for this Area Outside RT Room ZVB Manufacturer Beacon
FL Hosp. Tag # O2-000000311172 AIR-000000311173
Location IAW NFPA 99 Pass Labeled Pass Gauges Pass Leak Test Pass
Test Gauge O2 52 AIR 48
Pressure vs.
ZVB Gauge 52 50
Valve Size ¾” ¾”
Comments:
Gas/Pipeline Purity Oxygen Med Air Comments
Hydrocarbons <1 PPM <1 PPM
Dew Point -44F 5F
Carbon Monoxide <1 PPM <1 PPM
Carbon Dioxide 0 PPM 120 PPM
Gas Concentration 99%O2 21.8(%O2)
Particulates None None
Odor/Discoloration None None
Test Location RT RT
Area Alarm Panel Location for this Area NO ALARM FOR THIS ZONE
Corporate Office ∙ 4518 Clements Rd. Lakeland Florida 33811 Phone: 863-646-7555 ∙ Fax 863-646-2999
“Medical Gas Pipeline Equipment Service, Sales & Verifications”
©Daniel Voight 2009