Page 110 - 2018_IFC
P. 110

FIRE SERVICE FEATURES



                  8. Sprinkler valve and water-flow detector display             tanks, location of emergency generator and
                    panels.                                                      location of natural gas service;
                  9. Emergency and standby power status indicators.         13.6. Fire protection system information that
                                                                                 includes: location of standpipes, location of
                 10. A telephone for fire department use with controlled
                    access to the public telephone system.                       fire pump room, location of fire department
                                                                                 connections, floors protected by automatic
                 11. Fire pump status indicators.                                sprinklers and location of different types of
                 12. Schematic building plans indicating the typical floor       automatic sprinkler  systems installed
                    plan and detailing the building core,  means of              including but not limited  to dry,  wet and
                    egress,  fire protection  systems, fire-fighter air-         pre-action;
                    replenishment systems, fire-fighting equipment and      13.7. Hazardous material information  that
                    fire department access, and the location of fire walls,      includes: location and quantity of hazard-
                    fire barriers,  fire partitions,  smoke barriers and         ous material.
                    smoke partitions.
                                                                      14. Work table.
                 13. An  approved Building Information  Card that
                    includes, but is not limited to, all of the following  15. Generator supervision devices, manual start and
                    information:                                         transfer features.
                                                                      16. Public address system, where specifically required
                       13.1. General building information that includes:
                           property name, address, the number of         by other sections of this code.
                           floors in the building above and below     17. Elevator fire recall switch in accordance with
                           grade,  use and  occupancy classification     ASME A17.1/CSA B44.
                           (for mixed uses, identify the different types  18. Elevator emergency  or standby  power selector
                           of occupancies on each floor) and the esti-   switch(es), where emergency or standby  power  is
                           mated building population during the day,     provided.
                           night and weekend;
                       13.2. Building emergency contact information
                           that includes: a list of the building’s emer-            SECTION 509
                           gency contacts including but not limited to     FIRE PROTECTION AND UTILITY
                           building manager, building engineer and    EQUIPMENT IDENTIFICATION AND ACCESS
                           their respective work phone number, cell  509.1 Identification. Fire  protection equipment shall be
                           phone number and e-mail address;       identified in an approved manner. Rooms containing controls
                       13.3. Building construction information that  for  air-conditioning systems, sprinkler risers and valves, or
                           includes: the type of building construction  other fire detection, suppression or control elements shall be
                           including but not limited to floors, walls,  identified for the use of the fire department. Approved signs
                           columns and roof assembly;             required to identify fire protection equipment and equipment
                                                                  location shall be constructed of durable materials, perma-
                       13.4. Exit  access stairway and  exit stairway  nently installed and readily visible.
                           information  that includes: number of  exit
                           access stairways and  exit stairways in   509.1.1 Utility identification. Where required by the fire
                           building; each exit access stairway and exit  code official, gas shutoff valves, electric  meters, service
                           stairway  designation and floors served;  switches and other utility equipment shall be clearly and
                           location where each  exit access  stairway  legibly marked to identify the unit or space that it serves.
                           and  exit stairway discharges,  interior  exit  Identification shall be made in an approved manner, read-
                           stairways that are pressurized;  exit stair-  ily visible and shall be maintained.
                           ways provided with emergency lighting;  509.2 Equipment access. Approved access shall be provided
                           each exit stairway that allows reentry; exit  and maintained  for all fire protection equipment  to  permit
                           stairways providing roof  access; elevator  immediate safe operation and maintenance of such  equip-
                           information that includes: number of eleva-  ment. Storage, trash and other materials or objects shall not
                           tor banks, elevator bank designation, eleva-  be placed or kept in such a manner that would prevent such
                           tor car numbers and respective floors that  equipment from being readily accessible.
                           they serve; location of elevator machine
                           rooms, control rooms and control spaces;
                           location of sky lobby; and  location of                  SECTION 510
                           freight elevator banks;                  EMERGENCY RESPONDER RADIO COVERAGE
                       13.5. Building services  and system  information  510.1 Emergency responder radio coverage in new build-
                           that  includes: location of mechanical  ings. New buildings shall have approved radio coverage for
                           rooms, location of building management  emergency responders within the building based on the exist-
                           system, location and capacity of all fuel oil  ing coverage levels of the public safety communication sys-