FIRE PROTECTION AND LIFE SAFETY SYSTEMS



              that contains a bathtub or shower unless this would pre-  907.2.11.2 System response. The activation of two or
              vent placement of a smoke alarm required by Section  more smoke detectors,  a single smoke detector
              907.2.10.1 or 907.2.10.2.                            equipped with an alarm verification feature, the auto-
                                                                   matic sprinkler system or other approved fire detection
              907.2.10.5 Interconnection.  Where more than one
              smoke alarm is required to be installed within an indi-  device shall automatically do all of the following:
              vidual dwelling unit or sleeping unit in Group R or I-1  1. Cause illumination of the means of egress with
              occupancies, the smoke alarms shall be interconnected     light of not less than 1 footcandle (11 lux) at the
              in such a manner that the activation of one alarm will    walking surface level.
              activate all of the alarms in the individual unit.  Physi-  2. Stop  any conflicting or confusing sounds  and
              cal  interconnection  of  smoke alarms shall not  be      visual distractions.
              required where listed wireless alarms are installed and
              all  alarms sound upon  activation of one alarm. The   3. Activate an  approved directional  exit  marking
              alarm shall be clearly audible in all bedrooms over       that will become apparent in an emergency.
              background  noise levels with  all intervening doors   4. Activate a prerecorded message, audible through-
              closed.                                                   out the special  amusement building, instructing
                                                                        patrons to proceed to the nearest exit. Alarm sig-
              907.2.10.6 Power source. In new construction,
              required smoke alarms shall receive their  primary        nals  used in conjunction with the  prerecorded
              power from the building wiring where such wiring is       message shall produce a sound that is distinctive
              served from a commercial source and shall be equipped     from other sounds used during normal operation.
              with a  battery backup. Smoke alarms  with integral  907.2.11.3 Emergency voice/alarm communication
              strobes that are not equipped with battery back-up shall  system.  An emergency voice/alarm  communication
              be connected to an emergency electrical system  in   system, which is allowed to serve as a public address
              accordance with Section 1203. Smoke alarms shall emit  system, shall be installed  in accordance  with Section
              a signal when the batteries are low. Wiring shall be per-  907.5.2.2 and be audible throughout the entire special
              manent and without a disconnecting switch other than  amusement building.
              as required for overcurrent protection.            907.2.12 High-rise  buildings.  High-rise buildings  shall
                Exception:  Smoke  alarms are not required to  be  be provided with an automatic smoke detection system in
                equipped with battery backup where they are con-  accordance with Section  907.2.12.1, a fire  department
                nected to an emergency electrical system that com-  communication system in  accordance with  Section
                plies with Section 604.                          907.2.12.2 and an emergency voice/alarm communication
                                                                 system in accordance with Section 907.5.2.2.
              907.2.10.7 Smoke detection system. Smoke detectors
              listed in accordance with UL 268 and provided as part  Exceptions:
              of the building fire alarm system shall be an acceptable  1. Airport traffic control towers in accordance with
              alternative to single- and multiple-station smoke alarms
                                                                        Section 907.2.21 of this code and Section 412 of
              and shall comply with the following:                      the International Building Code.
                1. The fire alarm system shall comply with all appli-  2. Open parking garages in accordance with Section
                   cable requirements in Section 907.
                                                                        406.5 of the International Building Code.
                2. Activation of a smoke detector in a dwelling unit  3. Buildings with an  occupancy in Group A-5  in
                   or sleeping unit shall initiate alarm notification in  accordance with  Section 303.1 of the  Interna-
                   the dwelling unit or sleeping unit in accordance
                                                                        tional Building Code.
                   with Section 907.5.2.
                                                                     4. Low-hazard special  occupancies in  accordance
                3. Activation of a smoke detector in a dwelling unit    with Section 503.1.1 of the International Build-
                   or sleeping unit shall not activate alarm notifica-
                                                                        ing Code.
                   tion appliances outside  of the  dwelling unit or
                   sleeping unit, provided that a supervisory signal  5. Buildings with an occupancy in Group H-1, H-2
                   is  generated and monitored in  accordance with      or H-3  in  accordance with Section  415 of the
                                                                        International Building Code.
                   Section 907.6.6.
                                                                     6. In Group I-1 and I-2 occupancies, the alarm shall
           907.2.11 Special amusement  buildings. An automatic
           smoke detection system shall  be provided  in special        sound at a constantly attended location and occu-
                                                                        pant notification shall be broadcast by the emer-
           amusement buildings in  accordance with  Sections
                                                                        gency voice/alarm communication system.
           907.2.11.1 through 907.2.11.3.
              907.2.11.1 Alarm.  Activation of any  single smoke   907.2.12.1 Automatic  smoke detection. Automatic
                                                                   smoke detection  in high-rise buildings shall be  in
              detector, the  automatic sprinkler  system or any other
                                                                   accordance  with   Sections  907.2.12.1.1  and
              automatic fire detection device shall immediately acti-
              vate an audible and visible alarm at the building at a  907.2.12.1.2.
              constantly attended location from which emergency      907.2.12.1.1 Area smoke detection.  Area smoke
              action can be initiated, including the capability of man-  detectors shall be provided in accordance with this
              ual initiation of requirements in Section 907.2.11.2.  section. Smoke detectors shall be connected to an
         126                                                                        2018 INTERNATIONAL FIRE CODE ®