Page 165 - 2018_IFC
P. 165

FIRE PROTECTION AND LIFE SAFETY SYSTEMS



           protection  or  other features shall  thereafter be continu-  NFPA 72 for inspection, testing and maintenance of such
           ously maintained in accordance with applicable NFPA   systems. Records of inspection, testing and maintenance
           requirements or as directed by the fire code official.  shall be maintained.
           907.8.2 Testing. Testing shall be performed in accordance  907.9  Where  required in existing buildings and struc-
           with the schedules in NFPA 72 or more frequently where  tures.  An approved fire alarm system shall be provided in
           required by the fire code official. Records of testing shall  existing buildings and structures where required in Chapter
           be maintained.                                     11.
              Exception: Devices or equipment that are inaccessible  907.10 Smoke alarm maintenance. Smoke alarms shall be
              because of safety considerations shall be tested during  tested and maintained in accordance with the manufacturer’s
              scheduled shutdowns where approved by the fire code  instructions. Smoke alarms shall be replaced when they fail to
              official, but not less than every 18 months.    respond to operability tests, or when  they exceed 10 years
           907.8.3 Smoke detector sensitivity. Smoke detector sen-  from the date of manufacture, unless an earlier replacement is
           sitivity shall be checked within one year after installation  specified in the manufacturer’s published instructions.
           and every alternate year thereafter. After the second cali-
           bration test, where sensitivity tests indicate that the detec-
           tor has remained within its listed and marked sensitivity            SECTION 908
           range (or 4-percent obscuration light gray smoke, if not    EMERGENCY ALARM SYSTEMS
           marked), the length of time between calibration tests shall  908.1 Group H occupancies. Emergency alarms for the
           be permitted to be extended to not more than  5  years.  detection and notification of an emergency condition  in
           Where  the frequency  is extended, records of detector-  Group H occupancies shall be provided as required in Chap-
           caused nuisance alarms and subsequent  trends of these  ter 50.
           alarms shall be maintained. In zones or areas where nui-
           sance  alarms show any increase over the previous year,  908.2 Group H-5 occupancy. Emergency alarms for notifi-
           calibration tests shall be performed.              cation of an emergency condition in an HPM facility shall be
                                                              provided as required in Section 2703.12.
           907.8.4 Sensitivity test  method. To verify  that each                                                 *
           smoke detector is within its listed and marked sensitivity
           range, it shall be tested using one of the following meth-           SECTION 909
           ods:                                                          SMOKE CONTROL SYSTEMS
              1. A calibrated test method.                    909.1 Scope and purpose. This section applies to mechani-
              2. The manufacturer’s calibrated sensitivity test instru-  cal or passive smoke control systems where they are required
                ment.                                         for new buildings or portions thereof by provisions of the
                                                              International Building Code or this code. The purpose of this
              3. Listed control equipment arranged for the purpose.
                                                              section is to establish minimum requirements for the design,
              4. A smoke detector/control unit arrangement whereby  installation and acceptance testing of smoke control systems
                the detector causes a signal at the control unit where  that are intended  to provide  a tenable environment  for the
                the detector’s sensitivity is outside  its acceptable  evacuation or relocation of occupants. These provisions are
                sensitivity range.
                                                              not intended for the preservation of contents, the timely resto-
              5. Another calibrated sensitivity test method accept-  ration of operations or for assistance in fire suppression or
                able to the fire code official.               overhaul activities. Smoke control systems regulated by this
             Detectors found to have a sensitivity outside the listed  section serve a different purpose than the smoke- and heat-
           and marked sensitivity range shall be cleaned and recali-  removal provisions found in Section 910. Mechanical smoke
           brated or replaced.                                control systems shall not be  considered exhaust systems
                                                              under Chapter 5 of the International Mechanical Code.
              Exceptions:
                                                              909.2 General design requirements. Buildings, structures,
                1. Detectors listed as field adjustable shall be per-
                   mitted to be either adjusted within the listed and  or parts thereof required by the International Building Code
                   marked sensitivity range and cleaned and recali-  or this code to have a smoke control system or systems shall
                   brated or they shall be replaced.          have such systems designed in accordance with the applica-
                                                              ble requirements of Section 909 and the generally accepted
                2. This requirement shall not apply to single-station  and well-established principles of engineering relevant to the
                   smoke alarms.                              design. The construction documents shall include sufficient
              907.8.4.1 Sensitivity testing device.  Smoke detector  information and detail to describe adequately the elements of
              sensitivity shall not be  tested or measured using a  the design  necessary for the proper implementation of the
              device that administers an unmeasured concentration of  smoke control systems. These documents shall be accompa-
              smoke or other aerosol into the detector.       nied with sufficient information and analysis to demonstrate
                                                              compliance with these provisions.
           907.8.5 Inspection, testing and maintenance. The build-
           ing owner shall be responsible to maintain the fire and life  909.3 Special inspection and test requirements. In addition
           safety systems in an operable condition at all times. Ser-  to the ordinary inspection and test requirements that build-
           vice personnel shall meet the qualification requirements of  ings, structures and  parts thereof are  required to  undergo,

         132                                                                        2018 INTERNATIONAL FIRE CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   160   161   162   163   164   165   166   167   168   169   170